General Description:
22 AWG stranded (7x30) tinned copper conductors, Datalene® insulation, twisted pairs, overall Beldfoil®
shield (100% coverage) plus a tinned copper braid (65% coverage), drain wire, UV resistant PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material Dia. (mm)
1 22 7x30 TC - Tinned Copper 0.762
Total Number of Conductors: 2
Insulation
Insulation Material:
Insulation Trade Name Insulation Material
Datalene® FHDPE - Foam High Density Polyethylene
Outer Shield
Outer Shield Material:
Layer # Outer Shield Trade Name Type Outer Shield Material Coverage (%)
1 Beldfoil® Tape Aluminum Foil-Polyester Tape 100.000
2 Braid TC - Tinned Copper 65.000
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
22 7x30 TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVC - Polyvinyl Chloride
Overall Cable
Overall Nominal Diameter: 7.137 mm
Pair
Pair Color Code Chart:
Number Color
1 White/Blue Stripe and Blue/White Stripe
Pair Lay Length & Direction:
Lay Length (mm)
95.250
Mechanical Characteristics (Overall)
Operating Temperature Range: -20°C To +60°C
Non-UL Temperature Rating: 60°C
Bulk Cable Weight: 65.481 Kg/Km
Max. Recommended Pulling Tension: 266.892 N
Min. Bend Radius/Minor Axis: 71.120 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CM, PLTC
CEC/C(UL) Specification: CM
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
Page 1 of 3 08-26-2016
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION