Cut Sheet
For more Information
please call
1-800-Belden1
General Description:
20 AWG stranded (7x28) TC conductors, semi-rigid PVC insulation, twisted pairs, individually shielded
w/Beldfoil® (100% coverage), 22 AWG stranded TC drain wire, overall PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
2 20 7x28 TC - Tinned Copper
Total Number of Conductors: 4
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
S-R PVC - Semi-Rigid Polyvinyl Chloride 0.279
Inner Shield
Inner Shield Material:
Inner Shield Trade Name Type Inner Shield Material Coverage (%)
Beldfoil® (Z-Fold®) Tape Aluminum Foil-Polyester Tape 100
Inner Shield Drain Wire AWG:
AWG
22
Inner Shield Drain Wire Stranding: 19x34
Inner Shield Drain Wire Conductor Material: TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 1.0414
Overall Cable
Overall Nominal Diameter: 7.620 mm
Pair
Pair Color Code Chart:
Number Color
1 Red & Black
2 Green & White
Mechanical Characteristics (Overall)
Operating Temperature Range: -20°C To +80°C
UL Temperature Rating: 80°C (UL AWM Style 2464)
Bulk Cable Weight: 72.922 Kg/Km
Max. Recommended Pulling Tension: 320.270 N
Min. Bend Radius/Minor Axis: 76.200 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMG
CEC/C(UL) Specification: CMG
AWM Specification: UL Style 2464 (300 V 80°C)
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
Page 1 of 2 05-02-2016
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9402 Multi-Conductor - Audio, Control and Instrumentation Cable