PC-Tool User Manual
for Damper and Valve Actuators
For linear actuators, the stroke is displayed instead of the angle of rotation and the stroke
direction instead of the direction of rotation.
"Configuration" tab for linear actuators (excerpt)
Actuator number
Description 16 characters of any text
Position 16 characters of any text
Control signal Y
3-point AC voltage, positions: Open / neutral / closed
Open / closed DC or AC voltage, 2-point
DC 0–10 V (DC voltage)
Fixed operating range DC 0–10 V
DC 2–10 V modulating (DC voltage)
Fixed operating range DC 2–10 V
DC variable Start (Y=0%) 0.5 ... 30 V
Stop (Y=100%) 2.5 ... 32 V
Range between start and stop at least 2 V
PWM 0.02–5 s Duration of the control pulse (pulse width modulation),
fixed operating range
PWM 0.1–25.5 s Duration of the control pulse, fixed operating range
PWM 0.59–2.93 s Duration of the control pulse, fixed operating range
PWM variable Start (Y=0%) minimum 0.02 seconds
Stop (Y=100%) maximum 50 seconds