An existing value for Mid is automatically adapted when Min and Max are entered: If you enter
Min, Mid is always larger than or equal to this input value. If you enter Max on the other hand,
Mid is always less than or equal to this value.
Examples of settings for control signal Y / feedback U5
Control signal Y: 3...8 V min: 30%, max : 70%
Feedback U5 : 2...7 V start: 20%, stop: 90%
Y/U5
[V]
10
5
0
Open 100%
50%
Closed 0%
Position
Running time
In seconds Time needed to pass through the range limited by Min and Max (the valid
range of values for the running time depends on the actuator type and the
passed-through range).
Note: For actuators with the "constant speed" operating mode, the speed does not depend on
the range passed through. The running time refers to a fixed angle of 95° for rotary actuators or
a fixed stroke of 100 mm for linear actuators.