PC-Tool User Manual
for Damper and Valve Actuators
Synchronization at
Y = 0% Moves to the mechanical limit at zero stop (depending on the direction of
rotation / stroke direction)
Y = 100% Moves to the mechanical limit at full angle of rotation (depending on
direction of rotation / stroke direction)
Note: When the nominal setting range is set to "programmed", then the synchronization MUST
be carried out at Y=0%.
Torque (for full-rotation actuators) / Positioning force (for linear actuators)
25% ... 100% Can be set in increments of 25%. 100% corresponds to the maximum
torque / the maximum positioning force for the actuator type (see
nameplate)
Power ON
Synchronization Moves to a mechanical limit (according to the setting "Synchronization at")
Adaptation Moves to both mechanical limits and recalculates angle-dependent
parameters
Nothing (This option is not available for actuators of the "TOP" performance class.
When switched on, they must always be adapted or synchronized)
You can programmatically limit the rotation and stroke range at one end by only changing the
minimum or the maximum. If the value of Power ON is set to "Nothing", then the following holds
true:
The mechanical limit that can still be attained within a rotation range limited at one
end will be used for synchronization.
If you set the minimum to a value greater than 0%, the zero stop will no longer be in the range.
In this case, synchronization will take place at the end stop of the full damper opening (Y =
100%). If, on the other hand, you set the maximum to a value smaller than 100%,
synchronization will take place at the zero stop (Y = 0%).
This is also valid for the case that the nominal setting range is set to "programmed" and the
minimum is equal to 0%: The setting "Power ON: Nothing" is allowed.
Synchronization when the angle of rotation/stroke is limited at both ends
If the minimum is greater than 0% AND the maximum is smaller than 100%, then you can
select where the synchronization will take place. In this case, it is necessary to perform
synchronization or adaptation when you switch the device on (the setting "Power ON: Nothing"
is considered an error).
If the nominal setting range is set to "programmed" and the minimum is greater than 0%, then
the same rule applies: At least one synchronization must be programmed.