PC-Tool User Manual
for NV/NVF Series Actuators
Meaning of the settings
Control signal Y Type of control
Sensitivity Response sensitivity and reversal hysteresis of the
control function
Feedback U5 Type of feedback signal
Range Position range within the mechanical
limits
Running time Time needed to pass through the position range
Stroke Programmed stroke range: Max / Mid / Min
Direction of rotation Clockwise/counterclockwise (for full-rotation actuators)
Direction of stroke Plot of stroke direction to the positioning signal: Direct / inverted
(in acc. with switch S3.1)
Switching point Top / bottom (in acc. with switch S3.2)
Actuating force In percent of the maximum positioning force
Behavior in the event of bus
failure
Behavior when communication fails
Firmware Software version on the actuator
Config table ID Identification of the configuration table
Operating time Number of hours during which the actuator was
connected to the power supply
Active time Number of hours during which the actuator was mechanically in
motion and connected to the power supply
Stop & Go ratio Ratio of active time/operating time in percent. A high Stop & Go
ratio indicates an unstable control.
Running time, range, direction of rotation and stroke are not displayed on certain actuators.
2.2 Adaptation
In the adaptation, the actuator determines the range 0% ... 100% by approaching the
mechanical limits.
Click the "Adaptation" button on the Service tab.
Variant You can also trigger the adaptation directly on the actuator. To do this, you have to remove the
cover from the actuator. To trigger the adaptation, press the S2 button on the electronic PCB.