Multi-Function Technology
®
Operation
Motion Parameter Variables Description
New Generation AF
70 to 220 seconds Running time is selectable allowing for customizing the actuator for the
application at hand. Adjustable running time allows for:
• Matching HVAC system sequence of operation.
• Improving control loop stability.
• Reducing actuating noise (slower running).
• Retrofit applications
The running time is constant and independent of load.
New Generation NF
40 to 220 seconds
Running Time
AF / NF / LF / TF
75 to 300 seconds
GM
75 to 300 seconds
AM*
90 to 350 seconds
NM*
45 to 150 seconds
AH*
75 to 150 seconds
LM*
35 to 150 seconds
LH*
75 to 150 seconds
LU
75 to 150 seconds
Rotation
Direction of Rotation
Default or Reversed The direction of rotation can be "Direct" or "Reverse" acting of the control
signal. The direction of rotation is selected from a CW and CCW switch
located on the actuator.
An alternative method of changing the direction of rotation is to use the
PC-Tool software. This option allows you to make remote set-up corrections
without having the need to be at the actuator.
Selection of the direction of rotation is only possible via the PC-Tool
software or manually with the switch on the actuator. Selection via a preset
configuration is not an option.
Intermediate
Position
Control
(Override Control)
Minimum Position (Default 0%)
Intermediate Position (Default 50%)
Maximum Position (Default 100%)
Intermediate Positions are achieved
through ‘forced override’ positions.
SEE FIGURE A – FORCED OVERRIDES.
All intermediate settings are adjustable from 0 to 100%. Programmed as
default, these control positions are possible by using the wiring diagram in
FIGURE A. The override functions can be used as a means to test the
actuator’s functionality during equipment servicing or troubleshooting.
Intermediate positions can also be integrated into the control circuit as a
part of the sequence of operation.
The Min, Mid, and Max positions can be used in any MFT control mode.
VDC: For stand-alone controllers where a minimum position is needed.
PWM: Eliminate add-on accessories.
Floating Point: New functionality to a common application.
On/Off: New functionality to a common application.
Satisfy combustion air requirements or boiler sequencing with O/A damper.
– Eliminates secondary minimum position dampers.
* Quicker running actuators are available. Contact Belimo Customer Service for details.