PC-Tool User Manual
for ePIV Series Actuators
M40035 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
off Control function Y normal
(highest voltage = V’max)
Feedback U5 (active only if actuator address is set to PP)
Volumetric flow
0.5 … 10V
Volumetric flow feedback
0 … 100%, V'nom = 0.5 … 10V
Volumetric flow
2 … 10V
Volumetric flow feedback
0 … 100%, V'nom = 2 … 10V
Volumetric flow
variable
Volumetric flow feedback 0 … 100%, V'nom
Start 0.0 ... 8.0 volt / stop 2.0 ... 10.0V
Range between start and stop at least 2V
Characteristic curve
Equal percentage Characteristic curves for control function Y and feedback
U5 switched on (input signal to volume equal percentage)
Bus fail position
Last setpoint Volumetric flow in accordance with the last setpoint of the
MP master received
Open Open valve (100%, valve completely open)
Close Close valve
Max / V’max V’max volumetric flow
Synchronisation at
Y = 0% Approaching the mechanical limit with
zero end stop (valve closed)
Y = 100% Approaching the mechanical limit with full valve opening
With Power ON
Adaption Approaching both mechanical limits and recalculation of
angle-dependent parameters
Synchronisation Approaching one mechanical limit (in accordance with the
setting "Synchronisation at")
No action
Gear release button
Synchronisation (preset for EPIV actuators)