PC-Tool User Manual
for SY-MFT Series Actuators
3 Configuration
On the "Configuration" tab, you can read
out parameter values from the actuator,
change them and save them back to the
actuator. The valid ranges for the
parameter values are displayed in
parentheses next to the input boxes.
"Configuration" tab for SY-MFT actuators
Control Signal Y: Selectable: Options 2-10vdc, 0.5 – 10vdc, 4-20mA, DC Variable, 3 point*, Open/Close*
PWM 0.02-5s*, PWM 0.10-25.5s*, PWM 0.59-2.93s*, PWM Variable*
Feedback U5: Selectable: Options 2-10vdc, 0.5 – 10vdc, 4-20mA, DC Variable
*Available on 24MFT Actuator Models only.
What is “Loss of Signal functionality?
This is the point at which the SY actuator interprets no input from the controller and either stops, closes or opens the
valve based on the programmed control functionality.
Loss of signal point is always at 0.5V. It doesn’t matter if the control signal is 2-10V or 0.5-10V.
Loss of signal point is 1mA if 4-20mA is selected.
Loss of Signal – Stop The actuator will stop in its last position.
Loss of Signal – Open The actuator will move to its 100% position.
Loss of Signal – Close The actuator will move to its 0% position.
Loss of Signal – Nothing The actuator will move to the zero position.
Actuator number
1
Designation 16 characters of any text
Position 16 characters of any text
1
Only characters from the Western European character set are permitted for Description and
Position (refer to page 1-53).