800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
5-10
PC-Tool User Manual
for SY-MFT Series Actuators
Closing point (in acc. with switch S3.2)
top The linear spindle is moved into the actuator with the valve
closed and the stem is moved out of the fitting.
bottom The linear spindle is moved out of the actuator with the valve
closed and the stem is moved into the fitting.
Behavior in the event of bus failure (currently cannot be changed)
Last setpoint Position according to control signal Y
Sensitivity
Normal
Response sensitivity: 1%
@ Operating range
Reversal hysteresis 2.5%
@ Operating range
Damped
Response sensitivity: 2%
@ Operating range
Reversal hysteresis 5%
@ Operating range
Actuating force
25% ... 100% Can be set in increments of 25%. 100% corresponds to the
maximum positioning force for the actuator type (see nameplate
)
M40035 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.