Brochure

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
37
ZIP-RS232 US
For Interfacing PC with…MFT US Type Actuators
Technical data ZIP-RS232 US
Supply voltage 24 VAC; Class II power supply
Power consumption 1 W / 1.5 VA (without actuator)
Electrical protection MFT-XFMR is internally protected and
automatically resets
Connections Power supply Stereo connector
Actuator Manual push button terminals
MP-Bus Orange male connector, ZKS-MP (Optional)
RS232 PC cable, sub-D, 9 pin, female/female, included
Ambient temperature 0° to 122°F
Storage temperature -40°F to 176°F
Electrical safety Class III
Weight <1.0 lb. (without actuator)
Wiring Diagram
ZIP-RS232WirDiagRev_08
Standard Jumper Setting Jumper Setting for Null-Modem Cable
Null modem serial cables can be used by switching the internal jumpers.
Application
The ZIP-RS232 is used with the Belimo PC-Tool software (MFT-P US) to interface
all Multifunctional (…MFT US) type actuators via an RS232 port. Monitoring
and parameterization of one MFT actuator is enabled.
The ZIP-RS232 can also be used to interface the MFT actuators functionality via
the UK24LON.
Connection and Operation
Wiring Terminals
The …MFT US actuator wires are connected to the terminals and correspond to
the conductor wire designations. Some actuators are color coded and do not
have numbered conductors. The following indications should be used:
1 = Black
2 = Red
5 = Orange (non-spring, TF)
Green (LF)
White (AF, NF)
Switch
The Actuator On/Off switch on the ZIP-RS232 applies 24 VAC power to the
connected actuator. The ZIP-RS232 is powered when the MFT-XFMR is plugged
into a power receptacle.
RS232 Connector
The ZIP-RS232 is connected via this RS232 connector to the PC with a standard
female-female 9-pin sub-D cable, provided.
Power Supply
The MFT-XFMR accessory transformer is connected to the unit, and supplies 24
VAC power to the ZIP-RS232 and up to one connected actuator.
Power LED
A Green LED is lit when 24 VAC is supplied.
MP-Bus Connector
This connection is used only with the UK24LON or another MP-Master device.
Terminal Designations
U/PP: Data communications lead EN: Enabling signal for UK24LON
MP-Bus LED’s
Tx: LED flashes when data flows from ZIP-RS232 to the …MFT US actuator.
Rx: LED flashes when data flows from …MFT US actuator to ZIP-RS232
EN: LED is lit constantly when RS232 device is connected.
(E.g. PC is connected to ZIP-RS232)
Accessories
MFT-XFMR Power transformer
ZKS-MP MP-bus cable for use with UK24LON
ZIP-RS232