PC-Tool User Manual
3.4.2 Addressing with known serial numbers
Each MP/MFT actuator is delivered with a label containing its individual serial number. These
serial numbers can be used to assign a PP or an MP1 ... MP8 address to the actuator. An
additional, removable label with an identical serial number is supplied with the actuator. If the
actuator is installed at a particular position in the system, this additional label can be affixed at
the same position in the system diagram. This records where the actuator with the
corresponding serial number is located in the building. These serial numbers can be used to
assign the MP1 ... MP8 addresses to the actuators.
You can also fill in the input boxes manually before clicking Set Address, for example when the
buttons of the actuators are not accessible or you regularly take the serial numbers from your
documents.
3.4.3 Resetting actuator addresses
If you want to reset actuators with MP addressing to PP, click to the right of the MP-Channel
and select "De-address Device" in the pop-up menu.
Selection of the addresses to be reset
Mark the addresses whose actuators are to be de-addressed.
When the bus scan is set to MP/PP, the de-addressed actuators are no longer visible in the
outline bar [C] as long as there are still actuators with addresses.
If you set several actuators to PP, a bus jam will occur with the bus setting "PP only".