PC-Tool User Manual
Dialog for parameterizing limited lots
Select the file with the saved parameters in the dialog.
Position the cursor in the first input box for the serial number. Then press the acknowledge
button on the first actuator which should be parameterized. If the buttons are not accessible,
directly enter the serial numbers as described below.
The serial number of the actuator is read out after the acknowledgement and written into the
input box. The cursor jumps to the next line.
Repeat the process for all actuators that are to be parameterized and mark the checkbox if you
want to print labels after parameterization
(see Section 3.9 "Printing labels").
Click Parameterize.
The PC-Tool now asks for the file with the values to be written into the actuators.
The periodic bus scan is stopped for the duration of the parameterization. The actuators are
successively set to the address MP1, programmed and finally set to PP addressing.
When the bus scan is set to MP/PP, the actuators in the outline bar [C] will not be visible. If the
bus setting PP only is used, a bus jam will result.
If an error occurs during programming, a corresponding text is displayed in the "State" column.