Pre-Set MFT Confi gurations
Pulse Width Modulation Control
Application
How the MFT actuator performs is determined by the configuration (P-10001,
A01). The old generation actuators used a P-code (P-10001). The new
generation actuators use a shorter 3 digit code. This shorter code is displayed
on the reorder number.
P-2000… configuration types are used for Pulse Width Modulation control
outputs. Most D.D.C. controllers have digital outputs which incorporate a default
PWM range.
This enables a D.O. to be used as a proportional output when needed. Simply
select the appropriate configuration code according to your application.
Wiring Diagram
W041MFT
PWM, Triac Source and Sink
Spring Return Actuators
AFX24-MFT(-S) 180 in-lb
AF24-MFT(-S) US 133 in-lb
NFX24-MFT(-S) 90 in-lb
NF24-MFT US 60 in-lb
LF24-MFT(-S) US 35 in-lb
LF24-MFT(-S)-20 US 35 in-lb
TF24-MFT US 18 in-lb
Non-Spring Return Actuators
GMX24-MFT 360 in-lb
AMX24-MFT 180 in-lb
NMX24-MFT 90 in-lb
LMX24-MFT 45 in-lb
AH24-MFT 101 lbf
LH24-MFT 44 lbf
LUX24-MFT 27 in-lb
Select Configuration
Configuration Code Input Range Position Feedback Running Time Torque % Adaptation
Pulse Width Modulation
P-20001 W01 0.59 to 2.93 sec 2.0 to 10.0 VDC 150 100 MANUAL
P-20002 W02 0.02 to 5.00 sec 2.0 to 10.0 VDC 150 100 MANUAL
P-20003 W03 0.10 to 25.50 sec 2.0 to 10.0 VDC 150 100 MANUAL
P-20004 W04 0.10 to 25.60 sec 2.0 to 10.0 VDC 150 100 MANUAL
P-20005 W05 0.10 to 5.20 sec 0.5 to 5.0 VDC 150 100 MANUAL
P-20012 W12 0.50 to 25.50 sec 0.5 to 10.0 VDC 150 100 MANUAL
P-20013 W13 0.50 to 2.93 sec 0.5 to 5.0 VDC 150 100 MANUAL
P-20014 W14 0.10 to 10.00 sec 2.0 to 10.0 VDC 150 100 MANUAL
M40035 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.