Product Overview
151
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
AMCX24-MFT
Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology
®
Accessories
K-SA Reversible Clamp
ZG-100 Universal Mounting Bracket
ZG-101 Universal Mounting Bracket
ZG-103 Universal Mounting Bracket
ZG-104 Universal Mounting Bracket
Z-SMA AM/SM to AM Retrofit Mounting Bracket
ZG-AMA Crankarm Adaptor Kit
AV8-25 Universal Shaft Extension
ZG-JSA (-1, 2, 3) Jackshaft Adaptors for Hollow Jackshafts
ZS-100 Weather Shield - Steel
ZS-150 Weather Shield - Polycarbonate
ZS-260 Explosion Proof Housing
ZS-300 (-1) (-5) NEMA 4X Housing
Tool-06 8 mm & 10 mm Wrench
S1A, S2A Auxiliary Switch (es)
P370 Shaft Mount Auxiliary Switch
P…A Feedback Potentiometers
SGA24 Min positioners in NEMA 4 housing
SGF24 Min positioners for flush panel mounting
ADS-100 Analog to Digital Switch
ZG-R01 Resistor for 4 to 20 mA Conversion
NSV24 US Battery Back-Up Module
ZG-X40 Transformer
Note: When using AMCX24-MFT… actuators, only use
accessories listed on this page.
AMCX24-MFT - Typical Specification:
Proportional control damper actuators shall be electronic direct-
coupled type, which require no crankarm and linkage and be
capable of direct mounting to a shaft up to 1.05” diameter.
Actuators must provide proportional damper control in response
to a 2 to 10 VDC or, with the addition of a 500Ω resistor, a 4 to
20 mA control input from an electronic controller or positioner.
Actuators shall have Brushless DC motor technology and be
protected from overload at all angles of rotation. Actuators shall
have reversing switch and manual override on the cover. Run
time shall be constant and independent of torque. Actuators
shall be cULus listed, have a 5-year warranty, and be manufac-
tured under ISO 9001 International Quality Control Standards.
Actuators shall be as manufactured by Belimo.
AM
Wiring
1
2
Provide overload protection and disconnect as required.
Actuators may be connected in parallel if not mechanically mounted
to the same shaft. Power consumption and input impedance must
be observed.
3
Actuators may also be powered by 24 VDC.
Notes:
4
Position feedback cannot be used with a Triac sink controller.
The actuator internal common reference is not compatiable.
5
Control signal may be pulsed from either the Hot (Source)
or Common (Sink) 24 VAC line.
6
ZG-R01 may be used.
7
Contact closures A & B also can be triacs. A & B should
both be closed for triac source and open for triac sink.
8
For triac sink the common connection from the actuator
must be connected to the hot connection of the controller.
VDC/4-20 mA
6
Blk
(1) Common
Red
(2) + Hot
Wht
(3) Y
1
Input, 2 to 10V
Org (5) U Output, 2 to 10V
4 to 20 mA
or
2 to 10 VDC
Control Signal
Line
Volts
24 VAC Transformer
2
1
3
(+)
(–)
Ω
500Ω
1/4 watt
On/Off
Blk (1) Common
Red
(2) Hot
Wht
(3) Y Input
Org
(5) U Output
Line
Volts
24 VAC/DC Transformer
…MFT
a
Position
Feedback VDC
(+)
(–)
2
1
3
PWM
Blk (1) Common
Red
(2) + Hot
Wht
(3) Y Input
Org
(5) U Output
Line
Volts
24 VAC Transformer (AC only)
(+)
(–)
5
2
…MFT
…MFT
Position
Feedback VDC
1
Floating Point
…MFT
Line
Volts
2 to 10 VDC
Feedback Signal
24 VAC Transformer
Blk (1) Common –
Red
(2) Hot +
Wht
(3) Y
1
Input
Pnk
(4) Y
2
Input
Org (5) U Output 2 to 10V
1
3
5
4
2
A
B
7
8
W399
®