Product Overview

Technical data sheet G665C
www.belimo.com G665C • en-us • 2020-11-25 • Subject to change 1 / 2
Technical data
Functional data Valve Size 2.5" [65]
Fluid chilled or hot water, up to 60% glycol, steam
Fluid Temp Range (water) 32...338°F [0...138°C]
Fluid Temp Range (steam) 32...280°F [0...138°C]
Body Pressure Rating ANSI Class125, up to 175 psi below 150°F
Servicing repack/rebuild kits available
Rangeability Sv 85:1
Max Differential Pressure (Steam) 15 psi [103 kPa]
Flow Pattern 2-way
Controllable flow range stem up - open A – AB
Cv 65
Maximum Inlet Pressure (Steam) 35 psi [241 kPa]
ANSI Class 125
Body pressure rating note up to 175 psi below 150°F
Materials
Valve plug brass
Seat Stainless steel AISI 316
End fitting 125 lb flanged
Suitable actuators
Non-Spring EVB(X)
Electronic fail-safe AVKB(X)
Safety notes
WARNING: This product can expose you to lead which is known to the State of California to cause cancer
and reproductive harm. For more information go to www.p65warnings.ca.gov
The valve has been designed for use in stationary heating, ventilation and air-conditioning systems and
must not be used outside the specified field of application, especially in aircraft or in any other airborne
means of transport.
Only authorised specialists may carry out installation. All applicable legal or institutional installation
regulations must be complied during installation.
The valve does not contain any parts that can be replaced or repaired by the user.
When determining the flow rate characteristic of controlled devices, the recognised directives must be
observed.