Brochure
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
332
Typical ZG-110 Mounting
Duct
ZS-260 Explosion-proof Housing
For GM…, AM…, SM…, AF…, NF…, LF… Actuators
ZS-260 Shaft Thru Front
Drive Shaft
Front
Back
Bolt Housing
Conduit Holes
3/4-14 NPT
Rear Shaft
Location Plug
Anti-Rotation Strap
Pan
10
7
8
4
6
5
2
3
9
–AM
–LF
–SM
–GM
–AF/NF
–FM
–AM
–LF
–SM
–GM
–AF/NF
–FM
ZS-260 Mounting Instructions
1. Determine proper operating shaft location.
2. Remove threaded plug from the hole in which the
operating shaft will be mounted.
3. Install the anti-rotation strap, mounting plate, to the side
of the housing where the operating shaft will be
mounted.
4. From the inside surface of the housing, insert the
operating shaft, short length first, into the mounting
hole.
5. Hand tighten the shaft bushing into the housing until the
star nut/seal is in contact with the face of the housing.
6. Using a screw driver blade, drive the star nut/seal
clockwise until the bushing is locked into place.
7. Install the anti-rotation strap into the mounting plate at
the designated holes for the actuator to be used.
8. Install actuator.
9. Wire actuator (per electrical code).
10. Bolt housing together.
Typical ZG-109 Mounting
KH8 Crankarm
with Ball Joint (KG8 or KG10)
(order separately)
Push Rod (SH8 or SH10 )
(order separately)
ZG-110
ZS-260 Housing
(shaft through rear)
Mounting Hardware
(included with ZG-1
10)
Duct
Duct
K20901 - 01/09 - Subject to change. © Belimo Aircontrols (USA), Inc.