Submittal Sheet
Iron & Bronze Booster Pump Submittal A-120G
MODEL
NO.
FLANGE
SIZE NPT
INCHES
DIMENSIONS IN INCHES
(
MM
)
APPROX. SHPG.
WT. LBS.
(
K
g)
A B C
IRON
BODY
BRONZE
BODY
Series 100
3/4, 1,
1-1/4 & 1-
1/2
14-7/8
(378)
6-3/8
(162)
12-3/4
(324)
20
(9)
21
(10)
Series PR
3/4, 1,
1-1/4 & 1-
1/2
15-1/4
(387)
8-1/2
(216)
12-3/4
(324)
30
(14)
32
(15)
Series HV
1,
1-1/4 & 1-
1/2
15-3/8
(391)
8-1/2
(216)
13
(330)
28
(13)
30
(14)
2 2
16-5/8
(
422
)
8-1/2
(
216
)
14
(
356
)
36
(
16
)
39
(
18
)
2-1/2 2-1/2
17-1/4
(
438
)
10
(
254
)
14
(
356
)
54
(
24
)
58
(
26
)
LD3 3
17-1/4
(
438
)
10
(
254
)
14
(
356
)
53
(
24
)
57
(
26
)
HD3 3
17-1/2
(
444
)
10
(
254
)
14-1/4
(
362
)
55
(
25
)
59
(
27
)
PD-35S 3
20-1/4
(
514
)
12
(
305
)
16-7/8
(
429
)
75
(
34
)
80
(
36
)
PD-35T 3
20-1/4
(
514
)
12
(
305
)
16-7/8
(
429
)
75
(
34
)
80
(
36
)
PD-37S 3
20-1/4
(
514
)
12
(
305
)
16-7/8
(
429
)
75
(
34
)
80
(
36
)
PD-37T 3
20-1/4
(
514
)
12
(
305
)
16-7/8
(
429
)
75
(
34
)
80
(
36
)
PD-38S 3
22-11/16
(
576
)
14-1/2
(
368
)
18-15/16
(
481
)
128
(
58
)
138
(
63
)
PD-38T 3
23-15/16
(
608
)
14-1/2
(
368
)
20-3/16
(
513
)
125
(
57
)
135
(
61
)
PD-40S 3
24-3/4
(
629
)
14-1/2
(
368
)
21
(
533
)
130
(
59
)
140
(
64
)
PD-40T 3
21-7/8
(
556
)
14-1/2
(
368
)
18-1/8
(
460
)
127
(
58
)
137
(
62
)
Dimensions are subject to change.
Not to be used for construction
p
ur
p
oses unless certified.
TYPICAL SPECIFICATIONS
Electrical Box Arrangement for pumps with B&G Manufactured Motors
MODEL
NO.
#1 #2 #3 #4
Series 100
115 & 230Volt 60Hz 1PH
110 & 220Volt 50Hz 1PH
− − −
Series HV, PR & 2
115 & 230Volt 60Hz 1PH
110 & 220Volt 50Hz 1PH
− 3PH −
2-1/2", LD3 & HD3 − 1PH − −
PD35 & PD37 − −
A
LL −
PD38 & PD40 − − −
A
LL
The Contractor shall furnish and install In-The-Line pumps as illustrated on
the plans and in accordance with the following specifications:
1. The pumps shall be of the horizontal, oil-lubricated type. (Except PD-38,
PD-40 are permanentl
y
lubricated
)
Specificall
y
desi
g
ned and
g
uaranteed
for quiet operation. Suitable for 125# (862 kPa) working pressure.
2.The pumps shall have a
g
round and polished steel shaft with a hardened
inte
g
ral thrust collar. The shaft shall be supported b
y
two horizontal sleeve
bearings designed to circulate oil. (Except PD-38, PD-40 are
g
rease
lubricated ball bearin
g
desi
g
n
)
The pumps are to be equipped with a
mechanical seal with carbon seal face rotatin
g
a
g
ainst a ceramic seat. The
motor shall be non-overloading at any point on pump curve.
3. The motor shall be of the drip-proof, sleeve-bearing, (Except PD-38, PD-
40 are ball bearing) quiet operating, rubber-mounted construction. Motors
shall have built-in thermal overload protectors. (Exception - PD models with
3-phase motors, see paragraph 4.)
4. For PD models with 3-phase motors, add the followin
g
: The Contractor
shall furnish and install a ma
g
netic starter for each booster pump with at
least two thermal overload protectors. The starter shall be equipped with
manual reset buttons.
A
ll Units must be ITT Bell & Gossett Model No. ________, or approved
equal with capacit
y
of ______GPM at ______ft. head when directl
y
driven
throu
g
h a self ali
g
nin
g
flexible couplin
g
b
y
an oil lubricated motor,
_
____volts ____c
y
cle___phase.
Bell & Gossett
8200 N. Austin Avenue, Morton Grove, IL 60053
Phone (847)966-3700
Facsimile (847)966-9052
www.bellgossett.com