Brochure
CIRCULATORS ecocirc
®
XL
+LJKHIŵFLHQF\ODUJHZHWURWRUSXPSIRUKHDWLQJFRROLQJDQGSRWDEOHZDWHUV\VWHPV
Model Number
Nominal
Motor
HP
Dimenstions - Inches (mm)
Approx. Shipping
Weight Lbs. (kg)
A B C D E F Cast Iron Bronze
ecocirc XL 20-35 1/12 9.94 (252) 6.38 (162) 8.20 (208) 4.19 (106) 7.20 (183) 4.72 (120) 19.8 (9) 22 (10)
ecocirc XL 36-45 1/6 9.94 (252) 6.38 (162) 8.20 (208) 4.19 (106) 7.20 (183) 4.72 (120) 19.8 (9) 22 (10)
ecocirc XL 15-75 1/6 11.04 (280) 8.5 (216) 8.39 (213) 5.19 (132) 7.57 (192) 4.72 (120) 26.4 (12) 28.6 (13)
ecocirc XL 55-45 1/2 11.89 (302) 6.38 (162) 10.18 (258) 4.19 (106) 8.12 (206) 5.02 (127) 26.4 (12) 28.6 (13)
ecocirc XL 20-140 1/2 13.39 (340) 11.5 (292) 10.41 (264) 5.19 (132) 8.20 (208) 5.02 (127) 35.2 (16) 39.6 (18)
ecocirc XL 65-130 1 14.84 (377) 11.5 (292) 11.80 (299) 4.62 (117) 9.53 (242) 5.77 (146) 39.6 (18) 44 (20)
ecocirc XL 40-200 1 15.17 (385) 11.5 (292) 11.80 (299) 5.19 (132) 9.53 (242) 5.77 (146) 41.8 (19) 46.2 (21)
Model Number
Flange Size Inches
- NPT
# of
Bolts
Dimenstions - Inches (mm)
B&G Companion Fange
(Set of 2)
G H J K Cast Iron PN Bronze PN
ecocirc XL 20-35 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101001 - 101004* 101011LF - 101014LF*
ecocirc XL 36-45 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101001 - 101004* 101011LF - 101014LF*
ecocirc XL 15-75 2 4 5.18 (132) 4.06 (103) - 0.56 (14) 101215 10216LF
ecocirc XL 55-45 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101001 - 101004* 101011LF - 101014LF*
ecocirc XL 20-140 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 10216LF
ecocirc XL 65-130 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101005 - 101007* 101015LF - 101017LF*
ecocirc XL 40-200 2 4 5.19 (132) 5.19 (132) 4.06 (103) 0.56 (14) 101215 10216LF
3DUWQXPEHUVUHSUHVHQWD0DVWHU&DUWRQRIŶDQJHVZLWKIDVWHQHUVSDFN
1-1/2” is the diameter of the suction and discharge for the 2-bolt models.
STANDARD OPERATING MODES
Constant Speed
7KHSXPSPDLQWDLQVDFRQVWDQWVSHHGDWDQ\ŶRZUDWH7KHGHVLUHG
speed is set on the interface panel of the pump.
&RQVWDQW3UHVVXUHŊSF
7KHSXPSPDLQWDLQVDFRQVWDQWGLIIHUHQWLDOSUHVVXUHDWDQ\ŶRZ
demand until the maximum speed is reached. The desired head of
the pump can be set via user interface. Recommended for use in
systems with small or constant pressure losses.
3URSRUWLRQDO3UHVVXUHŊSY
The differential pressure continuously increases or deceases based
RQWKHŶRZGHPDQG7KHVHWSRLQWKHDGFDQEHVHWRQWKHSXPS
user interface. Use for systems with large pressure losses.
8
A
B
C
D
F
E
K
J
H
G
G
H
K
Night Time Setback
The pump will automatically reduce speed when there is
DQDEUXSWFKDQJHLQŶXLGWHPSHUDWXUH7KHFKDQJHLQŶXLG
temperature is from a boiler operating in night time setback
mode. The built-in temperature sensor is used. (Fixed Speed,
Constant Pressure, Proportional Pressure)
CONSTANT TEMPERATURE SPEED CONTROL
T- Constant Control
This control mode will use a PI algorithm to vary the speed of the pump
LQRUGHUWRPDLQWDLQDFRQVWDQWWHPSHUDWXUHRIWKHŶXLGPHGLD
Ŋ7&RQVWDQW&RQWURO
This control mode will use a PI algorithm to vary the speed of the pump
in order to maintain a constant differential temperature between the
built-in temperature sensor and external temperature sensor.