Submittal Sheet
Bell & Gossett
SUBMITTAL
A-526
Revision 8
JOB: REPRESENTATIVE:
UNIT TAG: SUBMITTED BY: DATE:
ENGINEER: APPROVED BY: DATE:
CONTRACTOR:
SCHEDULE
MAXIMUM WORKING PRESSURE: 125 PSIG (862 kPa) MAXIMUM OPERATING PRESSURE: 250°F (121°C)
TYPICAL SPECIFICATION
Thermoflo
®
Indicator
Engineered Products
DESCRIPTION
The Thermoflo Indicator is an indicating flow meter for measuring the
flow of heated or chilled water. Installed in each circuit of a hydronic
system, it permits simple balancing to meet design flow conditions.
CONSTRUCTION −SIZES 1-1/4" TO 2-1/2"
Fittings - bronze; connecting tube - copper, shut-off valves - brass;
indicator body - cast iron; indicator tube - Borosilicate glass; indicating
device Type 302 - stainless steel.
CONSTRUCTION - SIZES 3" TO 8"
Main body - steel pipe and flanges; other construction identical with
above.
MODEL NUMBER
SIZE
INCHES
FLOW RANGE
GPM (LITERS/MIN)
TAGGING INFORMATION QUANTITY
TFI-1-1/4 1-1/4 10-40 (37.8-151.4)
TFI-1-1/2 1-1/2 15-69 (56.8-261.2)
TFI-2 2 25-85 (94.6-321.8)
TFI-2-1/2 2-1/2 50-170 (189.3-643.5)
TFI-3 3 80-260 (302.8-984.2)
TFI-4 4 150-500 (567.8-1892.7)
TFI-5 5 250-750 (946.4-2839.0)
TFI-6 6 400-1000 (1514.2-3785.4)
TFI-8 8 700-1950 (2649.8-7381.5)
Furnish and install as shown on plans flow indicating devices of the
diverting type. Each device is to have a by-pass circuit containing a
flow indicator with shut-off valves to isolate all working parts from the
system and allow removal for cleaning without system shut-down.
Each unit shall be individually tested and calibrated by the
manufacturer and shall be suitable for operation at 125 psig (862
kPa) pressure and 250°F (121°C) temperature.
Units 2½" and smaller shall have copper solder joint connections;
units 3" and larger shall be 150# ANSI flanged. Design of units shall
permit installation in any position.
A
ll units to be ITT Bell & Gossett Model No. __________ Thermoflo
Indicators.
© COPYRIGHT 2002 ITT INDUSTRIES, INC.