Install Instructions

Figure 4: Vertical mode of discharge
Figure 5: Horizontal mode of discharge
4.1.4 Special installation
Installation with suction diffuser and triple-duty valve
Do not install and operate triple-duty valves and suction diffusers in closed systems unless
the system is designed with these safety and control devices:
Pressure relief valves
Compression tanks
Pressure controlling equipment
Temperature controlling equipment
Flow controlling equipment
Check that the control and safety devices have these characteristics:
Properly sized for their purpose
Placed correctly in the system before putting the system into operation
4.2 Connect the wiring
WARNING:
Disconnect and lock out electrical power before installing or servicing the unit.
Motors without built-in protection must be provided with contactors and thermal
overload protection for single-phase motors, or starters with heaters for three-phase
motors. (See the nameplate on the drive unit to select properly-sized overloads.)
Electrical Hazard:
Make sure that all connections are secure and the conduit box cover is closed before you
connect the electrical power.
1. Remove the screws that secure the conduit box cover.
2. Lift off the cover.
3. Attach the appropriately sized connector to the hole in the side of the conduit box.
4 Installation