Information

B E N N I N G W o r l d C l a s s T e s t E q u i p m e n t
pruefmes12s_kpl.qxd 25.06.2007 11:56 Uhr Seite 12
10162854.00 GB 06/2016 www.BN-Mediendesign.de Subject to technical changes. Printed on non-chlorine bleached paper.
Technical data BENNING SDT 1
Indication:
visually by means of three red signal LEDs for N, PE, L
conductor and LC display „
Voltage range: 230 V AC, ± 10 %
Frequency range: 50 Hz - 60 Hz
PE test response threshold: U
b < 50 V AC to earth
RCD testing current: I
n approx. 30 mA
Power supply: via test object (no batteries required)
Measuring category: CAT II 300 V
Safety: DIN EN 61010-1, DIN EN 61010-2-033
Appliance dimensions: 80 x 72 x 78 mm (l x w x h)
Weight: 70 g
Item no.: 020053
Recommended retail price: 49.90 €
BENNING SDT 1
BENNING SDT 1 socket tester with contact sensor for
active PE error detection and for testing the tripping
function of a 30 mA RCD
Application:
Quick and easy testing of shock-proof sockets, cable reels and
extension cables for correct connection.
Wiring errors and inadmissibly high contact voltages at the PE
connection are indicated directly.
In addition, it is possible to test the tripping function of a 30 mA
RCD by pressing the FI/RCD TEST key.
Testing functions:
Indication of correct wiring via LEDs.
Wiring errors such as missing PE, N and L conductors as well as an
inversion of the L and PE conductors are clearly indicated via three LEDs.
An active PE test by means of a contact electrode and via the LC
display warns of a dangerous contact voltage (> 50 V) being applied to
the PE connection.
• FI/RCD TEST key for testing the tripping function of 30 mA RCDs.
Features:
• Safe and easy operation by trained personnel
An easily understandable status table provides information about the
correct connection (OK, green) and the type of existing errors (red) at the
shock-proof socket.
Status table:
Your specialist dealer:
Socket is installed correctly, contact sensor checks the
PE contact for dangerous contact voltage
Socket with wiring error, danger to life! External conduc-
tor (L) and protective conductor (PE) have been inverted!
Testing the tripping function of a 30 mA RCD by pressing
the FI/RCD TEST key
X
B E N N I N G W o r l d C l a s s T e s t E q u i p m e n t
pruefmes12s_kpl.qxd 25.06.2007 11:56 Uhr Seite 12
Ihr Fachhändler:
BENNING Elektrotechnik und Elektronik GmbH & Co.KG
Münsterstraße 135-137
D-46397 Bocholt
www.benning.de
E-Mail: duspol@benning.de
B E N N I N G W o r l d C l a s s T e s t E q u i p m e n t
pruefmes12s_kpl.qxd 25.06.2007 11:56 Uhr Seite 12
Tel.: + 49 / (0) 2871 / 93-111
Fax: + 49 / (0) 2871 / 93-429