Instructions
BENNING IT 130  short instructions 
- 9 - 
1.6  Switch position „AUTO“ 
Turn the rotary selector switch to the "AUTO" position in order to select the measuring function by 
means of the "Commander" probe tip (10105455) or by means of the optional "Commander" test plug 
(044149). 
The following functions can be selected by means of the "Commander": 
  selection of the measuring function (only in the "AUTO" switch position) 
  start of measurement 
  storage of measuring results 
  LC display illumination ON/OFF 
  measuring point illumination ON/OFF 
1.7  Settings 
Turn the rotary selector switch to the "SETTINGS" position in order to make the following settings at 
the tester: 
  MEMORY (request data, delete data, delete entire memory) 
  SELECT LANGUAGE (GB, D, E, F, NL) 
  SET DATE/TIME 
  EARTHING SYSTEM (TN/TT or IT network) 
  RCD TESTING (according to EN 61008/EN 61009, IEC 60364-4-41, BS 7671, AS/NZS 3017) 
  SET ISC FACTOR setting (0.20 - 3.00) 
  SELECT COMMANDER (ON/OFF) 
  INITIAL SETTINGS 
  CLAMP SETTINGS (BENNING CC 1 (044037) , BENNING CC 2 (044110), BENNING CC 3 
(044038)) 
1.8  Measured value memory 
The internal memory of the tester allows to store up to 1800 measuring results including parameters, 
limiting values and sate/time of the measurement. 
The measuring results can be stored in a memory structure comprising 4 levels: 
Memory structure:        Example of installation structure: 
  [OBJ] OBJECT 001      customer Meyer 
  [BLO] BLOCK 001      distributor of ground floor 
  [FUS] FUSE 001      F1 kitchen 
  [CON] MEASURING POINT 001  socket 1 
Measurement:  no.: 1/3 RCD I:  22.5 mA 
no.: 2/3 R ISO:  >999 M 
no.: 3/3 R LOW: 0.17 
The PC software BENNING PC-Win IT 130 (included in the delivery) serves to read the memory of 
measured  values  of  the  tester  (download)  and  to  transmit  installation  structures  that  have  already 
been created on the PC to the tester (upload).