Instructions
BENNING IT 130  short instructions 
- 4 - 
 Warnings related to safety – measurements 
Insulation resistance 
  Insulation resistance measurement should only be performed on de-energized objects! 
  Do not touch the test object during the measurement or before it is fully discharged! Risk of 
electric shock! 
  When  an  insulation  resistance  measurement  has  been  performed on  a  capacitive object, 
automatic discharge may not be done immediately! The warning message   and the actual 
voltage are displayed during discharge until voltage drops below 30 V. 
  Do not connect test terminals to external voltage higher than 600 V (AC or DC) in order not to 
damage the test instrument! 
Low-impedance resistance/continuity test 
  Low-impedance resistance measurements/ continuity tests should only be  performed on de-
energized objects! 
  Parallel loops may influence on test results. 
Testing PE terminal 
  If the phase voltage is detected at the protective conductor connection PE, immediately stop 
all measurements and ensure that the fault of the installation will be eliminated. 
 Warnings related to safety – batteries/ storage batteries and fuses 
  Disconnect all test cables / accessories from the tester and from the installation and switch the 
tester off before opening the cover of the battery / fuse compartment. Dangerous voltages 
may be applied to the interior of the tester! 
  Please  make  sure  that  the  storage  batteries  are  inserted  correctly,  because  otherwise  the 
tester is not ready for operation and the storage batteries will discharge. 
  Do not recharge alkaline battery cells! 
  The storage batteries must be charged only by means of the charger included in the scope of 
delivery! 
 Warnings related to safety  – "Commander" probe tip (included in delivery) 
  – "Commander" test plug for shock-proof socket (optional) 
Measuring category of commanders: 
Tip "Commander" (cap off, 18 mm tip) ... CAT II 1000 V to earth 
Tip "Commander" (cap on, 4 mm tip) ..... CAT II 1000 V / CAT III 600 V / CAT IV 300 V to earth 
"Commander" test plug for shock-proof socket  CAT II 300 V to earth 
  Measuring category of commanders can be lower than protection category of the instrument. 
  If  dangerous  voltage  is  detected  on  the  tested  PE  terminal,  immediately  stop  all 
measurements, find and remove the fault! 
  Disconnect the "Commander" from the tester and from the installation and switch the 
"Commander" off before opening the cover of the battery compartment. Dangerous voltages 
might occur inside the "Commander"! 