Installation Tester BENNING IT 115 Short instructions GB: Detailed instruction manual on enclosed CD-Rom.
BENNING IT 115 Short instructions Benning Elektrotechnik & Elektronik GmbH & Co. KG Münsterstraße 135 - 137 D - 46397 Bocholt Phone: +49 (0) 2871 - 93 - 0 • Fax: +49 (0) 2871 - 93 - 429 www.benning.de • duspol@benning.de © 2015 BENNING This document must not be reproduced or used in any other form without the express written consent of BENNING. IDNR. 20 752 416 TN: 10141999.
BENNING IT 115 Short instructions Table of Contents 1 Start-up guide................................................................................................................................... 4 1.1 Safety and operational considerations .................................................................................... 4 1.2 Front and connector panel....................................................................................................... 6 1.3 Standard scope of delivery ............
BENNING IT 115 1 Short instructions Start-up guide 1.1 Safety and operational considerations The following symbols are used in the user manual and on the test equipment: Important, danger, must comply with documentation! Warning of electrical danger! Protection class II Ground (voltage to earth) Warnings related to safety – general information This document is not a supplement to the Instruction manual! Please find the operating manual as PDF file on the enclosed CD-ROM.
BENNING IT 115 Short instructions Warnings related to safety – measurements Insulation resistance Insulation resistance measurement should only be performed on de-energized objects! Do not touch the test object during the measurement or before it is fully discharged! Risk of electric shock! When an insulation resistance measurement has been performed on a capacitive object, automatic discharge may not be done immediately! The warning message and the actual voltage are displayed during discharge
BENNING IT 115 Short instructions 1.2 Front and connector panel Legend: 1 2 3 4 LCD UP DOWN TEST 128 x 64 dots matrix display with backlight. Modifies selected parameter. 5 6 7 8 ESC TAB Backlight, Contrast ON/OFF Starts measurements. Acts also as the PE touching electrode. Goes one level back. Selects the parameters in selected function. Changes backlight level and contrast. Switches the instrument power on or off.
BENNING IT 115 Short instructions Legend: Test connector Charger socket PS/2 connector Protection cover USB connector 1 2 3 4 5 Measuring inputs / outputs. For charging the rechargeable Ni-MH storage batteries Serial RS-232 interface for PC connection Without function 1.
BENNING IT 115 Short instructions 1.4 Indications and meaning of symbols Terminal voltage monitor The terminal voltage monitor displays on-line the voltages on the test terminals and information about active test terminals in the AC installation measuring mode. The voltage applied is displayed by means of the testing terminal symbol. All three testing terminals L, N and PE are used for the selected measurement. The voltage applied is displayed by means of the testing terminal symbol.
BENNING IT 115 Short instructions The test cable resistance for the low-impedance measurement / continuity test has been compensated. High resistance to earth of test probes. Results may be impaired. Measured signal is out of range (clipped). Results are impaired. Fuse F1 is broken. Sound warnings Continuous sound Warning! Dangerous voltage on the PE terminal is detected. Evaluation of the measuring result Measurement result is inside pre-set limits (green LEDs).
BENNING IT 115 Short instructions 1.7 Batteries and fuses Batteries Warning: Disconnect all test cables / accessories from the tester and from the installation and switch the tester off before opening the cover of the battery / fuse compartment.
BENNING IT 115 Short instructions Legend: 1 2 3 4 Fuse F1 Fuses F2 and F3 Serial number label Storage batteries/ batteries M 315 mA / 250 V F 4 A / 500 V (breaking capacity 50 kA) Size AA, rechargeable NiMH / alkaline quantity: 6 pieces 1.8 Calibration and Service Calibration To maintain accuracy of the measuring results, the device must be recalibrated in regular intervals by our factory service. We recommend recalibrating the device once a year. In case of need, please contact our service.
BENNING IT 115 Short instructions 1.9 Optional accessories Earthing set Earthing set consisting of 2 earth rods and 3 test cables 2 x L = 20 m, 1 x L = 4.5 m item no.: 044113 “Commander” test probe “TEST“ key for releasing the measuring process, “PASS“/“FAIL“ indication by means of green/ red LED, PE contact electrode for detecting the phase voltage at the protective conductor connection PE, key for measuring point and LCD illumination item no.
BENNING IT 115 2 Short instructions Measurements 2.1 Null balance (compensation) of the test cables 1. Set function Select R LOWΩ or CONTINUITY. R LOW Short-circuit the test cables. Shorted 3-wire test lead and optional “Commander” test probe (044155) 3. Press the key . 4. Press the key CAL. After performing test leads compensation first measured value and then 0.00 Ω is displayed. Successful compensation is displayed by means of the "CONTINUITY" function.
BENNING IT 115 Short instructions 2.2 TRMS voltage (V AC/DC), frequency and phase sequence (rotary field) 1. Set function V 2. Connection diagrams Connection of optional “Commander” test plug (044149) and 3-wire test lead in single-phase system Connection of the three-wire test cable and of the three-phase adapter (optional) (044148) in a three-phase system 3. The measuring result will be shown on the display. Uln .....Voltage between phase (L) and neutral conductors (N) Ulpe ...
BENNING IT 115 2.3 Short instructions Insulation Resistance (RISO) 1. Set function 2. Set parameters and limits. Test voltage [50 V, 100 V, 250 V, 500 V, 1000 V] Minimum limiting value [without (---), 0.01 MΩ ÷ 200 MΩ] R ISO 3. Connection diagrams Connection of 3-wire test lead and optional “Commander” test probe (044155) 4. Press and hold the key until result is stabilized. to start continuous measurement. Double-click („MΩ Ω“ flashes on display). Press the key again to finish the measurement. 5.
BENNING IT 115 2.4 Short instructions Low-impedance resistance (RLOW)/ continuity test 1. Set function 2. Set sub-function and limit. R LOWΩ Ω low-impedance resistance (testing current > 200 mA) or CONTINUITY (testing current < 8.5 mA) Maximum limiting value [without (---), 0.1 Ω ÷ 20.0 Ω] Buzzer [ON/OFF] only for CONTINUITY function R LOW 3.
BENNING IT 115 2.5 Short instructions Residual current operated device (RCD) 1. Set function 2. Set sub-function, parameters and limits. RCD I Tripping current RCD t Tripping time Uc Contact voltage AUTO automatic test Nominal tripping differential current I∆N [10/30/100/300/500/1000 mA]. RCD type [AC, A, F] Starting polarity [ , , Characteristic [selective FI/RCD , ] , general non- delayed , PRCD, PRCD-S, PRCD-K] Multiplication factor for test current [½ x I∆N, 1/2/5 x I∆N].
BENNING IT 115 2.6 Short instructions Loop impedance (Zs L-PE) 1. Set function 2. Set sub-function, parameters and limits. Loop impedance: Zs (for systems without RCD) Zs rcd (for systems with RCD) Fuse type [---, gL/gG, gG, B, C, K, D] Nominal current of the fuse Tripping time of the fuse ZS 3. Connection diagrams Connecting the optional “Commander” test plug (044149) and the 3-wire test lead 4. Press the key . 5. The measuring result will be shown on the display. Zs.....
BENNING IT 115 2.7 Short instructions Line impedance (ZI L-N/L) 1. Set function 2. Set sub-function, parameters and limits. Z Line Line impedance ∆U Voltage drop Fuse type [---, gL/gG , gG, B, C, K, D] Nominal current of the fuse Turn-off time of the fuse Maximum voltage drop [3,0 % ÷ 9,0 %] Zl 3.
BENNING IT 115 2.8 Short instructions Earth resistance (RE) 1. Set function 2. Set limits. EARTH RE Earth resistance Maximum limiting value [without, 1 Ω ÷ 5 kΩ] RE 3. Connection diagrams Connection of the optional earthing set (044113) 4. Press the key . 5. The measuring result will be shown on the display. R ...... Earth resistance Rp .... Probe resistance of the S probe (potential) Rc ....