Datasheet

12
BENNING IT 110, BENNING IT 120 B
Installation Testers
For safety tests on electrical systems
according to DIN VDE 0100 and IEC 60364
Multifunctional installation testers for complete testing and
efficient troubleshooting of electrical systems
• measurement of the protective conductor line and of the
equipotential bonding line with a testing current of 200 mA
• measurement of the insulation resistance with testing volt-
ages of 100 V, 250 V, 500 V and 1000 V
• line impedance and loop impedance measurement (optional
without tripping of the RCD) with calculation of the short-
circuit current (PFC/PSC)
• complete testing of RCDs with nominal fault currents of
10/30/100/300/500/1000 mA
• measurement of contact voltage (without tripping), tripping
time and tripping current (ramp test) of residual current
operated device (RCD)
• phase-sequence testing in three-phase mains
• voltage measurement up to 500 V and online voltage moni-
toring
Safety Instruments BENNING IT 101, IT 110 and IT 120 B
testing of electrical systems in compliance with the standards
BENNING IT 101
Insulation and Resistance Measuring Device
• measurement of insulating resistance and calculation of
the resulting leakage current
• testing voltages of 50 V, 100 V, 250 V, 500 V and 1000 V
• selectable limiting values for ISO measurement, green LED
for “PASS”, red LED for testing voltage/external voltage
• resistance measurement with a testing current of 200 mA
for testing protective conductor connections
• measurement of polarization index (PI) and dielectric
absorption rate (DAR)
• switchable probe tip for triggering the measuring process
internal memory for 100 measuring values per measuring function
• TRUE RMS voltage measurement with low-pass filter
• including case, switchable probe tip, silicone measuring
leads, magnetic hook, alligator clips, rubber protective
frame and batteries
BENNING
IT 101
indicating range 4000 digits (illumination)
low-impedance resistance
0.01 Ω – 40 Ω
insulation resistance 1 kΩ – 20 GΩ
resistance 0.01 Ω – 40 kΩ
voltage 0.1 V – 600 V AC/DC TRUE RMS
supplementary function leakage current, polarization index (PI),
dielectric absorption rate (DAR), automatic
discharge function, null balance of the
measuring leads
measured value memory 500 measuring results
measuring category CAT IV 600 V
item no. 044033
BENNING IT 101
Insulation and Resistance Measuring Device
IT 110
BENNING
IT 110
display graphic display (illuminated)
low-impedance resistance
0.01 Ω–2000
insulation resistance 1 kΩ–1000 MΩ
line impedance (L-N/L) 0.01 Ω–2000
loop impedance (L-PE) 0.01 Ω–2000
short-circuit current 0.01 A – 24.4 kA
RCD testing tripping time, tripping current,
type AC, A
contact voltage
phase sequence yes
voltage, frequency 1 V – 500 V, 45 Hz – 65 Hz
item no. 044100
BENNING IT 110
Installation Tester
B E N N I N G W o r l d C l a s s T e s t E q u i p m e n t
TRUE RMS
CAT IV 600 V
IT 101
Scope of delivery BENNING IT 101
BENNING TA 5
Optional accessories for
BENNING IT 101/IT 110/IT 120 B
40 m measurement cable BENNING TA 5 with practical winder, strap,
for the measurement of protective and bonding conductors,
connection: Ø 4 mm safety test
item no. 044039