Datasheet

14
B E N N I N G W o r l d C l a s s T e s t E q u i p m e n t
BENNNG PV 1-1 installation tester for photovoltaic systems
Commissioning tests and periodic inspection of PV systems
BENNING PV 1-1
scope of delivery
BENNING
PV 1-1
display graphic display (illuminated)
protective conductor
0.05 Ω – 199 Ω
resistance
insulating resistance 0.2 MΩ – 199 MΩ
open-circuit voltage
5 V to 1000 V DC
with polarity
short-circuit current 0.5 A to 15 A DC
DC string current/ 0.2 A to 40 A DC/AC
AC current (by means of BENNING CC 3)
insolation 100 to 1250 W/m
2
(by means of BENNING SUN 2)
PV module/ambient -30 °C to +125 °C
temperature (by means of BENNING SUN 2)
voltage via 4 mm sockets 30 to 440 V AC/DC
Interface/radio interface 1 x USB/433 MHz signal
dimensions/weight 270 x 115 x 55 mm/2.6 kg
scope of delivery carrying case, measuring lines,
alligator clips, MC4 and “Sunclix”
PV measuring lines, batteries, USB cable,
download software on CD-ROM
item no. 050421
BENNING PV 1-1
Installation tester for photovoltaic systems
Optional accessories for
BENNING PV 1-1
Current clamp adapter BENNING CC 3 for AC/DC current measurement
0.2 to 300 A AC/DC item no. 044038
Measuring line BENNING TA 5 for protective conductor measurement
Line length: 40 m item no. 044039
Application
For commissioning tests and periodic inspection of grid-con-
nected PV systems according to VDE 0126-23. Meets all
requirements necessary for system documentation of the
DC side. Ideal for troubleshooting, maintenance work and
performance evaluation of PV systems.
Features of the BENNING PV 1-1
• easy and safe operation by means of keys
• automatic test procedure for polarity, open-circuit voltage,
short-circuit current and insulating resistance
• RISO measurement with “PASS/FAIL” indication
• memory of measured values for 200 PV strings
• integrated real-time clock with date/time stamp for each
measurement
• USB interface and download software for the preparation of
test certificates in MS Excel
®
• safe contacting even during energy supply of the PV system
direct connection by means of MC4 and “Sunclix” connectors
Measuring functions
• continuity test of the protective conductor and of the
equipotential bonding conductor with a testing current of
200 mA
• polarity test of the DC current cables
• open-circuit voltage for each PV string of up to 1000 VDC
• short-circuit current for each PV string of up to 15 ADC
• insulating resistance with a testing voltage of 250 V, 500 V
and 1000 VDC
DC string current and AC current by means of BENNING CC 3
current measuring clamp up to 40 A AC/DC (optional)
Radio interface “Wireless SUN Link”
• wireless connection to the insolation and temperature
measurement instrument BENNING SUN 2 (optional)
• direct display of the insolation value in W/m
2
• storage of the electric quantities to be measured consider-
ing the insolation and the module/ambient temperature in
real time
BENNING PV 1-1
PV installation tester for testing
grid-connected PV systems
• tests in compliance with VDE 0126-23 (DIN EN 62446)
standard
easy – operation by means of keys with AUTO test procedure
• quick – testing within a few seconds only
• safe – contacting by means of PV connectors
BENNING TA 5 BENNING CC 3
Measured values transmitted
via wireless connection

Summary of content (1 pages)