User Manual
10/ 2013
BENNING PV 1-1
15
J
– PV test socket (black), for connecting the black safety measuring lead with PV connector
K – 4 mm test socket (black), for connecting the safety measuring lead with probe tip/ alliga-
tor clip
L + 4 mm test socket (red), for connecting the safety measuring lead with probe tip/ alligator
clip
A R
PE
voltage polarity indication, indicates the polarity of the DC voltage at the 4 mm test
sockets K and L. For AC voltage, “+” and “–“ are displayed alternately.
B
Current clamp measurement enabled
C
Ω
NULL
R
PE
null offset, is displayed in case of a compensation (null balance) of the measuring
lead resistance
D Attention, hot surface! If the symbol is displayed, immediately disconnect the
BENNING PV 1-1 from the PV generator. Connect the BENNING PV 1-1 only after the
symbol has disappeared.
E Polarity indication, indicates the polarity of the DC voltage at the PV test sockets
9
and
J
F
c
Attention, dangerous voltage has been detected
G R
PE
LOCK, enabled, if a continuous R
PE
measurement has been activated
H
m
Attention, if this symbol is activated, observe the instructions contained in the operating
manual in order to avoid danger.
I R
ISO
(pass)/ (fail), indicates whether the measured insulating resistance is within the
preset limiting values
J Selection of the insulation test voltage, displays the testing voltage of the insulating re-
sistance measurement
K Error, see specific error codes for further details (More details in chapter 9.1. “Error codes”)
L STORE, LCD data are stored in the internal memory
M RECALL, stored LCD data are loaded from the internal memory
N Storage location indicator, indicates the current storage location (1…200)
O Voltage / current deviation, indicates a deviation of the measured open-circuit voltage and
short-circuit current values of more or less than 5 %
P Battery symbol, is displayed to indicate discharged batteries
5. General information
The BENNING PV 1-1 is intended for electrical safety tests according to VDE 0126-23 (DIN EN
62446).
The BENNING PV 1-1 is not intended for continuous use. The BENNING PV 1-1 use is lim-
ited in use by delays in the rmware and also has temperature measuring circuits. If the inter-
nal temperature reaches the set limits then functionality will be reduced in order to allow the
BENNING PV 1-1 to cool down.
Do not leave the BENNING PV 1-1 attached to a hazardous voltage for extended periods of time
or while waiting for the BENNING PV 1-1 to cool down.
The BENNING PV 1-1 automatically tests connected PV modules or PV strings. All measuring
results are displayed on the large LC display.
- At full battery capacity, the BENNING PV 1-1 allows to carry out up to 3000 automatic mea-
surements of Vo/c, Is/c and R
ISO
(500 V).
- Appliance dimensions:
(L x W x H) = 270 x 115 x 55 mm
- Appliance weight: 2600 g
6. Environment conditions:
- The BENNING PV 1-1 is intended for making measurements in dry environment.
- Maximum barometric elevation for making measurements: 2000 m,
- Over voltage category/ Siting category: IEC/ EN 61010-1 → 1000 V category I (this apply to
the red
9
and black
J
PV test socket),
- Over voltage category/ Siting category: IEC/ EN 61010-1 → 300 V category III (this apply to
the red L and black K 4 mm test socket),
- Pollution Class 2,
- Protection Class: IP 40 (DIN VDE 0470-1 IEC/ EN 60529;
IP 40 means: Protected against objects >1mm, (4 - first index).
No protection against water, (0 - second index).
- EMC: IEC/ EN 61326,
- Operating temperature and relative humidity:
For operating temperature from 0 °C to 30 °C: relative humidity less than 80 %
For operating temperatures from 31 °C to 40 °C: relative humidity less than 75 %
- Storage temperature: The BENNING PV 1-1 can be stored at any temperature in the range
from - 25 °C to + 65 °C (relative humidity from 0 to 90 %). The battery should be taken out of
the instrument for storage.