User Manual

02/ 2018
BENNING CM 2
13
0.2 x (stated measurement accuracy) °C < 20 °C or > 26 °C with refer-
ence to the value at the reference temperature of 23 °C.
5.1.8 The BENNING CM 2 is supplied by 2 1.5 V batteries (IEC LR03/ ”Micro”).
5.1.9 When the battery voltage drops under the intended operating voltage of
the BENNING CM 2, a battery symbol appears in the display.
5.1.10 The service life of the battery is approx. 60 hours (alkali battery).
5.1.11 Dimensions of unit (length x width x height) = 192 x 66 x 27 mm.
Weight of unit: 205 g
5.1.12 The safety measuring leads and measurement tips supplied are spe-
cially suited to the rated voltage of the BENNING CM 2. The measuring
tips can be protected by caps.
5.1.13 Widest prong opening: 25 mm
5.1.14 Largest wire diameter: 22 mm
6. Ambient conditions
- The BENNING CM 2 is designed only for measuring in dry surroundings.
- Maximum barometric height during measurement: 2000 m
- Overvoltage category / set-up category: IEC 60664-1/ IEC 61010-1 → 300 V
category III, 600 V category II,
- Degree of contamination: 2
- Protection Class: IP 30 (DIN VDE 0470-1 IEC/ EN 60529)
IP 30 means: Protection against access to dangerous parts and protection
against solid impurities of a diameter > 2.5 mm, (3 - first index). No protec-
tion against water, (0 - second index).
- Operating temperature and relative humidity for voltage and resistance
measurements:
At operating temperature of 0 °C to 30 °C: relative humidity under 80%
At operating temperature of 30 °C to 40 °C: relative humidity under 75%
At operating temperature of 40 °C to 50 °C: relative humidity under 45%
- Operating temperature and relative humidity for current measurements:
At operating temperature of 0 °C to 30 °C: relative humidity under 80%
At operating temperature of 30 °C to 40 °C: relative humidity under 75%
- The BENNING CM 2 can be stored at temperatures from - 20 °C to + 60 °C.
The batteries must be removed from the unit.
7. Electrical data
Note: The measurement accuracy is stated as the sum of
- a relative proportion of the measurement value and
- a number of digits (i.e. numerical steps of the last place).
This measurement accuracy applies for a temperature of 23 °C ± 5 °C (23 °C ± 3 °C
for current measurement) and a maximum relative humidity of 80%.
The BENNING CM 2 has an automatic switch-over of measurement range.
Previous setting is therefore not required.
7.1 DC voltage range
The input resistance is 10 M.
Measuring range Resolution
Measurement accuracy
Overload protection
400,0 mV 100 µV ± (0,5 % of reading + 5 digits)
600 V
eff
600 V DC voltage
4,000 V 1 mV ± (0,5 % of reading + 2 digits)
600 V
eff
600 V DC voltage
40,00 V 10 mV ± (0,5 % of reading + 2 digits)
600 V
eff
600 V DC voltage
400,0 V 100 mV ± (0,5 % of reading + 2 digits)
600 V
eff
600 V DC voltage
600 V 1 V ± (0,5 % of reading + 2 digits)
600 V
eff
600 V DC voltage
7.2 AC voltage range
The input resistance is ≥ 10 MΩ parallel 100 pF. The measuring value is gained
and indicated as effective value (True RMS, AC coupling). Its calibration is
adapted for a sinusoidal curve form. With deviations from this form, the display
value becomes less accurate. The additional error for the following crest factors
is as follows:
crest factor of 1.4 to 2.0: additional error ± 1.0%
crest factor of 2.0 to 2.5: additional error ± 2.5%
crest factor of 2.5 to 3.0: additional error ± 4.0%