Operation Manual
22
Note:
- It is useful to deactivate the COMMANDER, if strong sources of interference might affect the
functioning of the COMMANDER.
4.4.6 Recalling original settings
The following parameters and settings can be set to initial (factory) values:
- Test parameters and limit values
- Contrast
- Prospective short/fault current scaling factor
- Supply system
- Communication port (BENNING IT 120 B only)
In order to recall the original setting press and hold the key and switch on the instrument. “Hard
reset” message will be displayed for a while.
Instrument settings, measurement parameters and limits are set to their initial values as follows:
Instrument settings Default value
Contrast 50 %
Prospective short/fault current scaling
factor
1.00
Supply system TN/TT
Communication port RS 232
Function
Sub-function
Parameter / limit value
CONTINUITY Sub-function: RLOW
LowΩresistance Highlimitresistancevalue:2.0Ω
Continuity Highlimitresistancevalue:20.0Ω
INSULATION RESISTANCE
Nominal test voltage: 500 V
Low limit resistance value: 1 MΩ
IMPEDANCE
(Zl)
(Zs)
Fusetype:noneselected(F)
Fusecurrentrating:noneselected(A)
Fusetrip-outcurrent:noneselected(ms)
RCD Sub-function: RCD Uc
Contactvoltage–RCDUc
Trip-outtime–RCDt
Trip-outcurrent–RCDIII
Autotest–RCDAUTO
Nominal differential current: I
∆N
=30 mA
RCD type and test current starting polarity:< G
Limit contact voltage: 50 V
Nominal differential current multiplier: ×1
LOOP IMPEDANCE TestingRCDswithnominaldifferentialcurrent≥10mA
RESISTANCE TO EARTH
(BENNING IT 120 B only)
Highlimitresistancevalue:50Ω
ILLUMINATION
(BENNING IT 120 B only)
Low limit illumination value: 300 lux