Figure 11.3: FI/RCD test in an IT system
11.3.4 First fault leakage current (ISFL)
TheISFLmeasurementiscarriedoutinordertomeasurethemaximumcurrentwhichcouldow
fromthetestedlineintotheprotectiveconductor.Thiscurrentowsthroughtheinsulatingresis-
tance and the insulation reactive impedance (capacitive) between the protective conductor and the
other conductors.
Howtomeasurethefaultcurrentincaseofarstfault:
Step 1 First select the ISOLATION/ INSULATION function by means of the function selector
switch.Then,selectthe„ISFL(rstfaultcurrent)“bymeansofthe▲/▼keys.Thefol-
lowing menu is displayed:
Figure 11.4: Measuring menu for fault current in case of a rst fault
Connect the test cable to the BENNING IT 120 B.
Step 2 Set the following limiting value:
- uppercurrentlimitfortherstfault
Step 3 Connect the test cable to the component to be tested. For carrying out the fault current
measurementfortherstfault,followtheconnectionplanshowningure11.5.Please
use the help function, if necessary.