Operation Manual

BENNING IT 130 short instructions
- 16 -
2.4 Low-impedance resistance (R
LOW
)/ continuity test
1. Set function
2. Set sub-function and limit.
R LOW
R LOW low-impedance resistance (testing
current > 200 mA) or CONTINUITY (testing
current < 8.5 mA)
Maximum limiting value
[without (---), 0.1 Ω ÷ 20.0 Ω]
Buzzer [ON/OFF] only for CONTINUITY
function
3. Connection diagrams
Connection of the three-wire test cable and of the optional measuring line BENNING TA 5 (044039)
Connection of 3-wire test lead and tip "Commander"
4.a R LOW low impedance
Press the key .
4.b CONTINUITY:
Press the key to begin performing a
continuous measurement.
Press the key TEST again to stop measurement.
5. The measuring result can be stored by means of the "MEM" key.
R ...... R LOW
R+ .... Result at positive polarity
R- ..... Result at negative polarity
R ...... CONTINUITY resistance