Operation Manual

08/ 2012 52 / 58
BENNING ST 750 A
Measurement acc. to measuring spec. / limiting value Tester acc. to regulation
Test socket (functional test after successful safety test) DIN VDE 0701-0702
DIN VDE 0751-1
DIN EN 61010-1
(VDE 0411-T1)
DIN EN 61557-1
(VDE 0413 T1)
DIN VDE 0404-1
DIN VDE 0404-2
DIN VDE 0404-3
Mains line (L and N) can be connected to test socket via relay, protective
conductor looped through (also PE jack!)!
Cut-offrelayto"tangible measuringjacks"contactclearanceof3mm, 80A
for max. 20 ms
Nominal voltage: 230 V ± 10 % (as mains feed-in!)
Rated current: 16 A
Max. breaking capacity (AC1): 3000 VA
Max. lamp load: 1000 W
Measuring range: 0.0 - 360 V AC (50 - 60 Hz)
0.10 - 20 A AC (50 - 60 Hz)
0 ... 4000 W (effective power)
0 ... 4000 VA (apparent power)
Resolution: 0.1 V
0.01 A
1 W
1 VA
Accuracy: U (V) ± 15% of the measured value
I (A) ± 15% of the measured value
P (W) ± 15% of the measured value
S (VA) ± 15% of the measured value
Measurement acc. to measuring spec. / limiting value Tester acc. to regulation
Safety extra-low voltage (PELV, SELV)
Measurement by means of probe
DIN VDE 0701-0702 DIN EN 61010-1
(VDE 0411-T1)
DIN EN 61557-1
(VDE 0413 T1)
DIN VDE 0404-1
DIN VDE 0404-2
DIN VDE 0404-3
Measuring range: 0.1 ... 360 V AC/DC
Resolution: 0.1 V
Accuracy: at 230 V AC ± 10 %
± 15% of the measured value