User's Guide

Depending on the number of Ranger Pro devices and their current sleep state, provisioning can
take up to several hours. If a device fails to join the network, see Reboot the Device on page27.
Before You Begin
If you are using a:
l Yokogawa or Honeywell ISA100 gateway, you must provision devices over the air.
l Bently Nevada Ranger Pro ISA100 gateway, Provision Using a USBNFCReader.
l WirelessHARTgateway, Provision Using a USBNFCReader.
ISA100 Devices
Ranger Pro ISA100 devices must be in an unprovisioned state to use over-the-air
(OTA)provisioning and join the network.
If over-the-air provisioning fails, you may be required to use the NFC reader and Ranger
Pro software to reboot or unprovision the device.
WirelessHART devices
Ranger Pro WirelessHART devices are shipped with an assigned Network ID and Join Key. The
default WirelessHART device values are:
l Network ID:32498
l Join Key: 00001631 00001631 00001631 00001631
If a Ranger Pro device does not join the network, it may be in a sleep state. It periodically wakes
from the sleep state to attempt to join the network. To reset the sleep cycle, see Reboot the
Device on page27.
ISA100 Sleep State
Once you install a battery into a Ranger Pro ISA100 device, it is ready to be provisioned over-the-
air or join the provisioned network. To conserve battery power, if a Ranger Pro ISA100 device is not
provisioned within a certain period of time, it enters a sleep cycle. It periodically wakes from sleep
mode to attempt to join the network. To reset the sleep cycle, see Reboot the Device on page27.
Interval after battery in inserted or sensor is disconnected from a
network:
Sensor tries to connect
every:
0 to 20 minutes 2 min
>20 min to 120 min 5 min
>120 min to 10 hours 15 min
>10 hours to 48 hours 30 min
>48 hours 60 min
20/57
Ranger Pro Wireless Condition Monitoring Device
User Guide 125M6113 Rev. F