User's Guide

b. Navigate to the Windows directory location of the device compatibility file you
previously downloaded from Bently Nevada tech support. Select the capability file
matching the device you want to upgrade, as shown below.
Ranger Pro Device Yokogawa Model Capability File Name
70M300 Repeater GE/70M300 BHGE-RP-70M300 v6.1.CFF
70M301 Single Axis GE/70M301 BHGE-RP-70M301 v6.1.CFF
70M303 Tri-Axis GE/70M303 BHGE-RP-70M303 v6.1.CFF
c. Click Open. The CFfile is displayed in the CFFile field.
6. Select the CFfile compatible with the devices displayed in the Device Tag field.
7. For each type of Ranger Pro device, modify these Concentrator OID:11 Read Parameters:
OID Concentrator
Value
70M300 Repeater 70M301 Single Axis 70M303 Tri-Axis
Update policy Periodic Periodic Periodic
Publication period 0 (zero) 150 150
Stale limit Default 5 5
Retry mode Normal Normal Normal
8. For each type of Ranger Pro device, verify these additional Concentrator OID:11 Read
Parameters:
OID Parameter 70M300 Repeater 70M301 Single Axis 70M303 Tri-Axis
UAPMO
Diag_Status
To prevent session timeout, select the
UAPMO Diag_Status
parameter (if
displayed)and click the "<" button. The parameter is moved to the list of
Available Parameters
.
AI_01AI_02AI_03AI_04
AI_05 AI_06 AI_07 AI_08
Not available AI_01 - AI_05: available
AI_06 - AI_8: unavailable
AI_01 - AI_08: available
9. For each type of Ranger Pro device, configure the Concentrator OID:12 Read Parameters.
OID Concentrator
Value
70M300 Repeater 70M301 Single Axis 70M303 Tri-Axis
Update policy Default Periodic Periodic
Publication period Default 10 10
Stale limit Default 10 10
Retry mode Default Normal Normal
22/57
Ranger Pro Wireless Condition Monitoring Device
User Guide 125M6113 Rev. F