User's Guide

To configure a Ranger Pro device using a NFCReader:
1. Open the Ranger Pro Configuration Software.
2. Connect the USBNFC reader to the computer running the Ranger Pro software.
3. Place the Ranger Pro device upside down on the NFC reader pad.
4. Select the NFC Manager tab. All sensors and their current status are displayed.
5. Select a sensor device. Verify that the NFC status in the footer is Ready.
6. Choose a configuration mode:
o
To modify the existing device configuration, select Configuration Manager > Live.
o
To apply a default configuration or custom configuration template, select
Configuration Manager > Preset.
Shorter vibration and temperature periods reduce battery life.
7. Unsaved changes are highlighted in blue. To save the changes, click Apply. Pending
changes are displayed in orange. Completed changes are displayed in black.
8. If the sensor is currently publishing data, wait two measurement intervals for the new units
to take effect.
For ranges and complete specifications, see the Ranger Pro Datasheet (document 125M5237).
Advanced Settings
After you connect to a gateway, you can view device settings. These include three features that
provide detailed data.
Data on Demand
Use this option to request immediate data. Data is displayed within 8 to 10 minutes. The most
recently scheduled measurements, if any, are canceled. Any additional measurements are
delayed 90 minutes.
Data on Vibration
Use this option to set a vibration threshold which, when exceeded, enables display of overall or
dynamic measurements. This can be useful for low vibration machines or machines that are not
currently running.
l If vibration is below the threshold, overall values are published as zero and dynamic
measurement transfers are skipped.
l If vibration is above the threshold, data is published and transferred as configured.
Data on Severity
Use this option to display data depending on the severity of the vibration based on user-defined
limits.