Owner`s manual

86 | P a g e
Address
R/W
Name
Conversion
Notes
4202
R/W
ClipperCmdVolts
([4202] /10) Volts
Variable Voltage command to
Clipper or Aux in Clipper mode
4203
R/W
WindNumberOfPoles
[4203] poles
Number of turbine alternator
poles (for RPM Calc)
4204
R/W
MppPercentVoc
[4204] 00 to 100 %
% of Voc for U-Set mode
4205
R/W
WindTableToUse
[4205]
FUTURE power curve select
4206
R/W
WindTableLearn
[4206]
FUTURE Wind Learn usage
4207
R/W
LEDmode
[4207]
See Table 4207-1
4208
4209
RESERVED
4210
4211
4212
4213
R/W
ID name
[4210]
MSB
|| [4210]
LSB
||
[4210]
MSB
|| [4210]
LSB
||
[4210]
MSB
|| [4210]
LSB
||
[4210]
MSB
|| [4210]
LSB
|| (End
with 00 if less than 8
characters)
Unit Name. DHCP and
MODBUS name. 8 character
maximum ASCII. Takes
place of MODBUS address
in MNGP display if present
(this needs some work)
4214
4215
W
CTIME0
([4215] << 16) + [4214]
(possibly atomic op)
Consolidated Time Registers
SEE Table 4214-1
4216
4217
W
CTIME1
([4217] << 16) + [4216]
(possibly atomic op)
Consolidated Time Registers
SEE Table 4216-1
4218
W
CTIME2
[4218]
Consolidated Time Registers
SEE Table 4218-1
4219
R/W
BaudRateStopStartEtc
[4219] Baud rate, bps
(Not implemented as of May
2011)
MODBUS Serial Baud rate.
Note that writing this register
will immediately change the
target unit’s serial baud rate
which may result in
communication problems
with other units in the system
including the unit’s MNGP.
4220
R/W
RemoteMenuMode
[4220]
Present Remote Menu sent
from MNGP
4221
R/W
RemoteButtons
[4221]
Remote Buttons pressed from
MNGP
4222
R/W
VbatOvrshootSenstvty
[4222]
Overshoot Sensitivity (not
implemented)
4223
R/W
RESERVED
[4223]
RESERVED (Do NOT
Write)
4224
R/W
PreVoc
([4224] /10) Volts
PV Terminal V before Relay