11. System Single Line Diagram
AC
INPUT
SHORTING
MIDNITE SOLAR
TURBINE CONTROL BOX
V(in) = 480VAC
V(out) = 600VDC
I(out) = 52A
CHASSIS
15A
P3P2
3
4
DC
P1
15A
(OPTIONAL)
LA
5
CHASSIS
GROUND ROD AT
BASE OF TOWER
(OPTIONAL)
6
LA
5
-
+
BAT
PV
BATTERY
BANK
4
3 x #8AWG CU + #10AWG CU GND
WIRE FOR RUNS BETWEEN 180 TO
300 FEET (INCLUDING TOWER
HEIGHT). REFER TO THE
INSTALLATION MANUAL FOR OTHER
CONFIGURATIONS AND DISTANCES.
MIDNITE SOLAR
CLASSIC 250
V(in) = 250VDC
V(out) = 48VDC
I(out) = 52A
XL.1 WIND TURBINE
1kW 3Ø OUTPUT
I(max) = 15A, V(max) 180VAC
3
INDOORS
OUTDOORS
NOTES:
1. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70 NEC ARTICLE 694.
2. SYSTEM SHALL BE INSTALLED ONLY BY QUALIFIED PERSONS PER NEC 705-6.
3. PROVIDE WARNING SIGN PER NEC 694-22(A)(4) READING "WARNING. ELECTRIC SHOCK HAZARD. DO NOT
TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND THE LOAD SIDE MAY BE ENERGIZED IN THE OPEN
POSITION.
4. MARK DISCONNECT "WIND ELECTRIC SYSTEM DISCONNECT" PER NEC 694.22(C)(2).
5. LIGHTNING ARRESTOR INSTALLED AT TOWER-BASE DISCONNECT SWITCH OR POWERCENTER.
6. MOUNT DISCONNECT / J-BOX ON SEPERATE POST. DO NOT MOUNT TO THE TOWER.
BERGEY WINDPOWER
NORMAN, OKLAHOMA
Figure 12: Single Line Diagram (Typical)