Installation, Use and Care Manual

14
GASCONNECTION
All gas connections must comply with national
and local codes. The gas supply line (service )
must be the same size or greater than the inlet
lineof the appliance. Thisrange uses a1/2"NPT
inlet (see drawing below for details of gas
connection). On all pipe joints use appropriate
sealant
resistanttogas.
This range can be used with Natural or
LP/Propane gas. The range is shipped from the
factoryforusewithnaturalgas.
For LP/propane household installation, the
appliance must be converted by the dealer, by a
factorytrained professional or by a qualified
licensedplumberorgas
servicecompany.
Gasconversionisimportantforsafeandeffective
useoftheappliance.Itistheresponsibilityofthe
dealerandtheowneroftherangetoperformthe
appropriate gas conversion following the
directionsofthemanufacturer.
THEGASCONVERSIONPROCEDUREIS
DESCRIBEDINTHISMANUALANDINTHE
PACKAGECONTAININGTHECONVERSION
NOZZLESSHIPPEDWITHEVERYRANGE.
Pleaseprovidetheservicepersonwiththis
manualbeforeworkisstartedontherange.
WARNING!
DONOTUSEANOPENFLAMEWHENCHECKING
FORLEAKS!
Leak testing of the appliance shall be conducted
according to the manufacturer's instructions.
Before placing
the oven into operation, always
check for leaks with soapy water solution or
otheracceptablemethod.
Check for gas leakage with soapy water solution
or other acceptable methods in all gas
connections installed between inlet gas pipe of
the appliance, gas regulator, till to the manual
shutoffvalve.
MANUALSHUTOFFVALVE
THISVALVEISNOTSHIPPEDWITHTHE
APPLIANCEANDMUSTBESUPPLIED BYTHE
INSTALLER.
The manual shutoff valve must be installed in
the gas service line between the gas hookup on
the wall and the appliance inlet, in a position
whereitcan
bereachedquicklyintheeventofan
emergency.
In Massachusetts: A 'T' handle type manual gas
valve must be installed in the gas supply line to
thisappliance.
FLEXIBLECONNECTIONS
In case of installation with flexible couplings
and/or quickdisconnect fittings, the installer
must use a heavyduty, AGA
designcertified
commercial flexible connector of at least 1/2"
(1.3 cm) ID NPT (with suitable strain reliefs) in
compliance with ANSI Z21.41 and Z21.69
standards.
In Massachusetts: The unit must be installed
witha36"(3foot)longflexiblegasconnector.
InCanada:useCAN16.1088metalconnectors
forgasappliancesandCAN16.9M79quick
disconnectdeviceforusewithgasfuel.
PRESSURETESTPOINTSTOPPERVALVE
To avoid gas leaks, the pressure testpoint
stoppervalveandgasketsuppliedwiththerange
mustbeinstalledonthegasfittingatthebackof
therange
accordingtothediagrambelow.
