Make-Up Air Damper Application Guide
Broan Automatic Make-Up Air Damper Product Guide – 04-17-13    12 
-  When multiple Dampers are required, Up to four Slave Dampers may be directly 
connected to any primary Damper (whether LinkLogic™, Direct-Wired, or 
Universal) to increase the available make-up air volume. 
7.  Planning the Installation 
Planning the installation first requires selecting the most appropriate installation approach. The 
chart below offers suggestions for the most effective installation approach by considering a few 
important factors. Further details on the two main types of installations are provided below. 
7.1 Sizing the Damper & the Duct 
The required amount of make-up air will vary for each home, depending on the home 
characteristics, the amount of exhaust ventilation provided within the home, and the local 
building code requirements. A well designed solution considers the home size, the home’s air 
tightness, the exhaust rate, the presence of combustion appliances, and the installation 
configuration of the Damper. To assist building professionals in specifying code-compliant 
makeup air solutions and developing product-specific cut-sheets, Broan-NuTone has developed 
an on-line tool called the Range Hood Make-Up Air Specifier, available on Broan, BEST, and 
NuTone websites. 
If you’re a homeowner who’s not interested in the technical details of sizing make-up air 
systems, feel free to jump ahead to section 7.1.3.