Make-Up Air Damper Application Guide
Broan Automatic Make-Up Air Damper Product Guide – 04-17-13    14 
One of the key functions of the Tool is its ability to allow users to take credit for make-up air that 
is supplied through cracks and gaps within the building envelope. While the building code 
requires that some of the make-up air for range hoods over 400 cfm be provided through a 
system that can be “automatically controlled to start and operate simultaneously with the 
exhaust system” (e.g., the Broan Automatic Make-Up Air Damper), it also recognizes that some 
make-up air can be provided through air leakage across the building envelope. Using 
engineering equations
5
, the Tool makes it easy to estimate the expected amount of make-up air 
that can be provided at the user-selected design depressurization limit, both naturally through 
leakage across the building envelope and intentionally through automatically opening the 
Damper(s). To avoid double-counting building openings used for combustion air, the Tool has 
the user input the cross sectional area of any combustion air openings for combustion 
appliances that are not direct-vent appliances. 
Finally, the Tool outputs a cut-sheet of the recommended make-up air solution, including a list of 
user-selected range hood, Damper(s), design performance characteristics, and information that 
can be submitted to the code official to demonstrate code compliance. 
7.1.2  Simplified Sizing in the Absence of Building Codes 
The Tool is configured to provide code-compliant make-up air system specifications for kitchen 
exhaust systems exceeding 400 cfm. In the case where make-up air is not required by code, but 
the designer believes that the building’s performance would benefit from installing the Broan 
Automatic Make-Up Air Damper, the following rule of thumb is offered: Select a Broan 
Automatic Make-Up Air Damper such that the Damper diameter is greater than or equal to the 
exhaust duct diameter. 
7.1.3 Testing 
Regardless of the make-up air sizing method selected, Broan highly recommends that a 
qualified HVAC professional be consulted after installation to ensure that the 
  Damper opens and closes as designed, 
  Depressurization is not excessive during operation of exhaust appliances, and 
  Exhaust and combustion appliances operate as designed.  
Where combustion appliances are located within a home’s pressure boundary, a combustion 
appliance zone test performed by a qualified HVAC professional is recommended. Note that 
other systems and features of the home can also create negative pressures in the home relative 
to outdoors, and that the Damper is not intended to address these. 
7.2 Outdoor Air Intake Location 
Proper design and location of the outdoor air intake location is critical in ensuring that the 
Damper can safely and reliably provide an opening for fresh outdoor air to enter the home. The 
following requirements for the location of the outdoor air intake should be met: 
-  Outdoor air intake is located a minimum of 10’ from combustion appliance vents, 
chimneys, plumbing stacks, and bathroom or kitchen exhaust vents. If local codes have 
more stringent separation requirements, they shall apply. 
5
 The Tool uses the Darcy-Weisbach equation and others sourced from ASHRAE Fundamentals 2009, 
Chapters 16 and 21. 










