Make-Up Air Damper Application Guide
Broan Automatic Make-Up Air Damper Product Guide – 04-17-13    15 
-  If integrated with the return trunk of the central duct system, the outdoor air intake is 
located at least 10’ from the HVAC appliance. 
-  Outdoor air intake is placed high enough above grade to prevent blockage from snow or 
other debris such as leaves, and at a minimum of 1’ above grade. 
-  Make-up air damper should not
 draw air from crawlspaces, garages, attics, adjacent 
dwelling units, or any enclosed part of the building. The Damper should be installed to 
draw air directly from outdoors. 
7.3 Outdoor Air Intake Opening Protection 
Because the Damper, together with the end cap and outdoor air duct which are installed with it, 
will allow outdoor air into the indoor environment, it is important to meet the following 
requirements: 
-  Install the protective screen provided with your Damper to protect the opening to the 
outdoor air duct 
-  If a protective screen other than the screen provided with your Damper is used, it must 
cover the entire opening of the outdoor air duct. This screen must also have openings of 
at least ¼” but no larger than ½” 
-  The outdoor air intake opening should meet local code provisions for the protection of 
openings in exterior walls, including steps to prevent moisture intrusion around the 
opening. 
Note that the screen over the outdoor air opening is not a filter. It is intended to prevent the 
intake of leaves, animals, or debris into the outdoor air duct. A downstream filter is necessary to 
remove pollen, dust, and other airborne particles. Potential filter locations are shown below in 
the Typical Installations section (section 8). 
7.4 Climatic Considerations for Outdoor Air (OA) Ducts Connected to Central Duct Systems 
If connecting the OA duct to the return side of a central duct system, check to see if the HVAC 
equipment manufacturer has any minimum requirements for the air temperature in the return air 
plenum (a minimum of 60°F return temperature for gas-fired forced air furnaces is 
recommended by some manufacturers). The installer should adjust both the size of the OA duct 
and the location of its connection to the return side of the central duct system so that minimum 
air temperature requirements are satisfied under design conditions. While the volume of OA 
that can be provided will vary between locations, the following guidance is offered as a rule of 
thumb: 
International Energy 
Conservation Code 
Climate Zone 
Maximum Recommended 
Outdoor Make-Up Air Flow as % 
of Total Furnace Air Handler Flow 
1 No limit 
2 40% 
3 30% 
4 25% 
5 20% 
6 15% 
If necessary, homes with more than one central HVAC system may increase the OA volume by 
installing OA ducts with Dampers on each system. 










