Data Sheet
BP-SUC-D
Supercap packs (DIN rail)
Long-life storage medium for UPS systems
High reliability
Maintenance-free supercap technology
High cycle stability > 500 000
Extended temperature range
High power density
Integrated control circuitry
Over current protection
Over voltage protection (up to 30 V)
Connect / disconnect power function
Ruggedly constructed DIN rail version
Technology EDLC (Electric double-layer capacitors) – Supercaps
Life cycles >500.000
Temperature Operating: -20…+70 °C / Storage: -20…+70 °C
Max. operation altitude 5000 m
Communication SMB
Nominal backup time, measured at +21 °C
50 W 100 W 140 W
BP-SUC-1011D
~ 20 sec ~ 8 sec –
BP-SUC-1020D
~ 40 sec ~ 16 sec –
BP-SUC-1615D
~ 29 sec ~ 14 sec ~ 10 sec
BP-SUC-2120D
~ 39 sec ~ 19 sec ~ 14 sec
Back up time depends on battery capacitance, load and temperature.
Bicker Elektronik GmbH | 86609 Donauwörth | Germany
Tel. +49 906 70595-0 | info@bicker.de | www.bicker.de
Delivery
5
YEARS
Delivery
5
YEARS
Technical data
UPS systems
DC UPS
Extended
Extended
Product specific data
P/N BP-SUC-1011D BP-SUC-1020D BP-SUC-1615D BP-SUC-2120D
UPS version UPSI-1208D UPSI-1208D UPSI-2406D UPSI-2406D
Nominal voltage 10.4 V DC 10.4 V DC 15.6 V DC 20.8 V DC
Number of used cells 4 cells à 2.6 V
(serial)
8 cells à 2.6 V
(serial and parallel)
6 cells à 2.6 V
(serial)
8 cells à 2.6 V
(serial)
Energy 1.8 kJ (useful 1.1 kJ) 3.6 kJ (useful 2 kJ) 2.7 kJ (useful 1.5 kJ) 3.6 kJ (useful 2 kJ)
ESR 10 mΩ 10 mΩ 10 mΩ 10 mΩ
Charge voltage 10.4 V DC 10.4 V DC 15.6 V DC 20.8 V DC
Charge current 4 A max. 4 A max. 3 A max. 3 A max.
Discharge current 17 A max. 17 A max. 18 A max. 18 A max.
Fuse (SMD) 20 A / 32 V 20 A / 32 V 20 A / 32 V 20 A / 32 V
Dimensions (Wx D x H) 63x100x120 mm ±0.5 mm 63x100x120 mm ±0.5 mm 63x100x120 mm ±0.5 mm 63x100x120 mm ±0.5 mm
Weight (net) 310 g 400 g 350 g 400 g
NEW