- Index
- A Brief specification
- B Intended use
- C Technical Data
- D Name / Address / Support E-Mail / Phone number of the manufacturer
- E General Data
- E1 Assembly and installation advice
- E2 Convection and installation position
- E3 Description of connectors
- E4 Dimensioning the upstream power supply
- E5 Initial operation
- E6 Connection
- E7 Overview connector / counterpart with description / Scope of delivery
- E8 Charging time
- E9 Reverse polarity / Overload / Short circuit
- E10 Backup time
- E11 Behaviour in case of exceeding maximum backup time
- E12 Status LED
- E13 Software
- E14 Recommendations for a long UPS service life
- E15 Maintenance
- E16 Disposal
- E17 Disclaimer
- E18 Preventive measures and rules when operating the UPS system
UPSI-2406DP1 | UPSI-2406DP2
Revision 1-3
10
OUTPUT DATA – UPSI-2406DP1 / UPSI-2406DP2 (NORMAL MODE)
Unless otherwise stated, all specifications apply to 25° C ambient temperature,
24 V DC input voltage and nominal output current (I
N
).
Output voltage 24 V DC
Output voltage range U
OUT
= U
IN
– 0.5 V DC max. (depending on load)
Capacitive load 3000 µF (at start)
Output current
I
N
I
STAT.BOOST
I
DYN.BOOST
I
SFB
4 A
4.125 A
n. a.
30 A (5 ms)
Output power
P
N
(U
N
, I
OUT
= I
N
, I
CHARGE
= 0)
P
STAT.BOOST
(U
N
, I
OUT
= I
STAT.BOOST
, I
CHARGE
= 0)
P
DYN.BOOST
(U
N
, I
OUT
= I
DYN.BOOST
, I
CHARGE
= 0)
96 W
99 W
n. a.
Short-circuit proof Yes
No-load proof Yes
OUTPUT DATA – UPSI-2406DP1 / UPSI-2406DP2 (BACKUP MODE)
Unless otherwise stated, all specifications apply to 25° C ambient temperature,
24 V DC input voltage and nominal output current (I
N
).
Output voltage 23.5 V DC
Output voltage range n.a.
Output current
I
N
I
STAT.BOOST
I
DYN.BOOST
I
SFB
4 A
4.125 A
n. a.
30 A (5 ms)
Output power
P
N
(U
N
, I
OUT
= I
N
, I
CHARGE
= 0)
P
STAT.BOOST
(U
N
, I
OUT
= I
STAT.BOOST
, I
CHARGE
= 0)
P
DYN.BOOST
(U
N
, I
OUT
= I
DYN.BOOST
, I
CHARGE
= 0)
96 W
99 W
n. a.
Short-circuit proof Yes
No-load proof Yes