Instructions
Table Of Contents
- Index
- A Brief specification
- B Intended use
- C Technical Data
- D Name / Address / Support E-Mail / Phone number of the manufacturer
- E General Data
- E1 Assembly and installation advice
- E2 Convection and installation position
- E3 Description of connectors
- E4 Dimensioning the upstream power supply
- E5 Initial operation
- E6 Connection
- E7 Overview connector / counterpart with description / Scope of delivery
- E8 Charging time
- E9 Reverse polarity / Overload / Short circuit
- E10 Backup time
- E11 Behaviour in case of exceeding maximum backup time
- E12 Status LED
- E13 Software
- E14 Recommendations for a long UPS service life
- E15 Maintenance
- E16 Disposal
- E17 Disclaimer
- E18 Preventive measures and rules when operating the UPS system
UPSI-2406DP1 | UPSI-2406DP2
Revision 1-3
12
CONNECTION DATA – RELAY
Connection labeling RL
Switch contact (floating) Relay
Status (configurable) Power Fail Alarm
State condition (configurable) Input voltage <22.5 V DC
Switching voltage 24 V DC / 125 V AC
Current carrying capacity 1 A (DC) / 0.5 A (AC)
State - signal assignment NO (Normaly Open) / NC (Normaly Closed) –
configurable via Software
Connection method Plug connection (screwless)
Conductor cross-section solid 0.205 mm … 1.3 mm (24 … 16 AWG)
Conductor cross-section flexible 0.205 mm … 1.3 mm (24 … 16 AWG)
Conductor cross-section with ferrule 0.205 mm … 1.3 mm (24 … 16 AWG)
Stripping length 7 mm … 9 mm
DATA INTERFACE – USB
Interface designation USB
Numbers of interfaces 1
Connection method USB type B (female)
Locking No
Transmission physics USB 2.0
Topology Point-to-point
Protocol VCOM, HID battery
Transmission length ≤3 m
Access time <1 s
Chipset NXP
Electrical isolation No