Instructions
Table Of Contents
- Index
- A Brief specification
- B Intended use
- C Technical Data
- D Name / Address / Support E-Mail / Phone number of the manufacturer
- E General Data
- E1 Assembly and installation advice
- E2 Convection and installation position
- E3 Description of connectors
- E4 Dimensioning the upstream power supply
- E5 Initial operation
- E6 Connection
- E7 Overview connector / counterpart with description / Scope of delivery
- E8 Charging time
- E9 Reverse polarity / Overload / Short circuit
- E10 Backup time
- E11 Behaviour in case of exceeding maximum backup time
- E12 Status LED
- E13 Software
- E14 Recommendations for a long UPS service life
- E15 Maintenance
- E16 Disposal
- E17 Disclaimer
- E18 Preventive measures and rules when operating the UPS system
UPSI-2406DP1 | UPSI-2406DP2
Revision 1-3
15
INTERFERENCE IMMUNITY ACCORDING TO 61000-6-2 (INDUSTRY SECTOR)
Basic standard CE Normative minimum requirements EN 61000-6-2 (CE)
(Interference immunity of industrial environment)
Electrostatic discharge
EN 61000-4-2
Housing contact discharge
Housing air discharge
Comment
4 kV (test level 2)
8 kV (test level 3)
Criterion A
Electromagnetic HF field
EN 61000-4-3
Frequency range
Test field strength
Frequency range
Test field strength
Frequency range
Test field strength
Comment
80 MHz … 1 GHz
10 V/m (test level 3)
1.4 GHz … 2 GHz
3 V/m (test level 2)
2 GHz … 2.7 GHz
1 V/m (test level 1)
Criterion A
INTERFERENCE IMMUNITY ACCORDING TO EN 61000-6-2 (INDUSTRY SECTOR)
Basic standard CE Normative minimum requirements EN 61000-6-2 (CE)
(Interference immunity of industrial environment)
Fast transients (Burst)
EN 61000-4-4
Input
Output
Signal
Comment
0.5 kV (test level 1 symmetrical)
0.5 kV (test level 1 symmetrical)
0.5 kV (test level 1 symmetrical)
Criterion A
Surge voltage load (Surge)
EN 61000-4-5
Input
Output
Signal
Comment
0.5 kV (test level 1 symmetrical)
0.5 kV (test level 1 symmetrical)
0.5 kV (test level 1 symmetrical)
Criterion A
Power frequency magnetic field immunity
EN 61000-4-8
Comment Criterion A