Instructions
Table Of Contents
- Index
- A Brief specification
- B Intended use
- C Technical Data
- D Name / Address / Support E-Mail / Phone number of the manufacturer
- E General Data
- E1 Assembly and installation advice
- E2 Convection and installation position
- E3 Description of connectors
- E4 Dimensioning the upstream power supply
- E5 Initial operation
- E6 Connection
- E7 Overview connector / counterpart with description / Scope of delivery
- E8 Charging time
- E9 Reverse polarity / Overload / Short circuit
- E10 Backup time
- E11 Behaviour in case of exceeding maximum backup time
- E12 Status LED
- E13 Software
- E14 Recommendations for a long UPS service life
- E15 Maintenance
- E16 Disposal
- E17 Disclaimer
- E18 Preventive measures and rules when operating the UPS system
UPSI-2406DP1 | UPSI-2406DP2
Revision 1-3
24
E11 Behaviour in case of exceeding maximum backup time
When the given buffering times are exceeded, the output is separated on the basis of the discharge voltage of
the corresponding storage medium (total discharge protection).
For supercapacitors, which are not sensitive to a deep discharge, a threshold has been definded which is limi-
ted by the current. The lower the voltage, the higher the current on the capacitors at constant output power.
If more than 70 % of the maximum allowable output current is consumed during discharge of the supercapa-
citors, the converter will shut down without immediately dis connecting the output and a lower voltage will
appear at the output (state <2 s). This condition should be avoided by shutting down the system in time before
discharging the supercapacitors under high currents.
E12 Status LED
1 x flash, pause 1,5 s Status: Battery start
2 x flash, pause 1,5 s Status: Capacity for start is required, state charging
3 x flash, pause 1,5 s Status shutdown: Waiting for shutdown completion
4 x flash, pause 1,5 s Status reboot: Output is switched off and time runs until restart (Reboot)
5 x flash, pause 1,5 s Status: No battery recognized
6 x flash, pause 1,5 s Battery voltage too high, battery disabled
7 x flash, pause 1,5 s Charge current too high, battery disabled
1 Hz flash > power fail
Status: Backup mode
Always on Status: System OK
Quick flashing Critical Error
Status: output voltage too low
> UPS will be shut down
Status: Overcurrent detected
> UPS will be shut down