Input voltage 24 V DC (22.530 V)
Input current 4.9 A max.
Output voltage Normal mode: V
IN
– 0.5 V DC max. (depending on load)
Backup mode: 23.5 V DC
Output current 4 A nominal
Capacitive load 3000 µF (at start)
Charging method CC / CV / CP
Protection Overcurrent protection, Reverse polarity protection,
Deep discharge protection (only DP1)
Interface USB, RS232, USB-HID
Type of battery DP1: Li-Ion 2.5 Ah / 37 Wh
DP2: EDLC 3.5 kJ / 0.972 Wh useful
Ambient temperature Operating: DP1: 0…+50° C / DP2: -20…+65° C
Storage / Transport: DP1: -20…+50° C / DP2: -30…+65° C
Operation altitude ≤4000 m
Humidity ≤95 % (at 25° C, no dew)
Dimensions W/ H / D 63 x 120 x 100 mm ±0.5 mm
Weight 0.6 kg
Technical Data
A Brief specification
UPSI-2406DP1
|
UPSI-2406DP2
24 V DC / 4 A
24 V DC UPS (DIN rail version)
Integrated Li-Ion batteries (DP1) OR
maintenance-free Supercaps (DP2)
Cycle Life 500 (DP1)
|
>500 000 (DP2)
Intelligent power sharing
Regulated output voltage in backup mode
Minimum load detection
Power fail Timer-Funktion
Relay dry contact on power fail
USB & RS232 Interface
HID control center
Reboot-Funktion
Fuel gauge