Instructions
Table Of Contents
- Index
- A Brief specification
- B Intended use
- C Technical Data
- D Name / Address / Support E-Mail / Phone number of the manufacturer
- E General Data
- E1 Assembly and installation advice
- E2 Convection and installation position
- E3 Description of connectors
- E4 Dimensioning the upstream power supply
- E5 Initial operation
- E6 Connection
- E7 Overview connector / counterpart with description / Scope of delivery
- E8 Charging time
- E9 Reverse polarity / Overload / Short circuit
- E10 Backup time
- E11 Behaviour in case of exceeding maximum backup time
- E12 Status LED
- E13 Software
- E14 Recommendations for a long UPS service life
- E15 Maintenance
- E16 Disposal
- E17 Disclaimer
- E18 Preventive measures and rules when operating the UPS system
UPSI-2406DP1 | UPSI-2406DP2
Revision 1-3
9
INPUT DATA – UPSI-2406DP1 / UPSI-2406DP2
Unless otherwise stated, all specifications apply to 25° C ambient temperature,
24 V DC input voltage and nominal output current (I
N
).
Input voltage 24 V DC
Input voltage range 22.5 V DC…30 V DC
Electric strength max. 35 V DC
Fixed connect threshold
Undervoltage
Voltage drop Input/Output
22.5 V DC
0.5 V DC max. (depending on load)
Current draw
I
N
(U
N
, I
OUT
= I
N
, I
CHARGE
= 0)
I
MAX
(U
N
, I
OUT
= I
STAT.BOOST
, I
CHARGE
= max)
I
NO-LOAD
(U
N
, I
OUT
= 0, I
CHARGE
= 0)
I
CHARGE
(U
N
, I
OUT
= 0, I
CHARGE
= max)
4.1 A
4.9 A
100 mA
DP1: 1.8 A / DP2: 1.5 A
Power consumption
P
N
(U
N
, I
OUT
= I
N
, I
CHARGE
= 0)
P
MAX
(U
N
, I
OUT
= I
STAT.BOOST
, I
CHARGE
= max)
P
CHARGE
(U
N
, I
OUT
= 0, I
CHARGE
= max)
98.4 W
117.6 W
DP1: 43.2 W / DP2: 36 W
Internal input fuse Yes (15 A)
Switch-on time < 5 s
Switch-on time in battery mode (Bat.-Start) n. a.
C Technical Data
C1 General Technical Data