Installation Guide

Power Supply
110–125 VAC 1 Φ
10 A 50/60 Hz
Controller
Input Cable
CAT5 Cable
To wall
controller
Wall Controller
Power Supply
Cable
L1/AC LINE BLACK
PE/GROUND GREEN OR BARE COPPER
L2/AC NEUTRAL WHITE
WHITE
GREEN
BLACK
BLUE YELLOW
WWW.BIGASSSOLUTIONS.COM © 2015 DELTA T CORP. ALL RIGHTS RESERVED.
22
WIRING DIAGRAMS & ELECTRICAL GUIDELINES
WARNING: To reduce the risk of electric shock, wiring should be performed by a qualified electrician!
Incorrect assembly can cause electric shock or damage the motor and the controller! Hazard of electrical
shock!
WARNING: The installation of a Big Ass Fan must be in accordance with the requirements specified in this
installation manual and with any additional requirements set forth by the National Electric Code (NEC),
ANSI/NFPA 70-2014, and all local codes. Code compliance is ultimately YOUR responsibility!
CAUTION: The product warranty will not cover damage or failure caused by improper installation.
WARNING: Exercise caution and common sense when powering the fan. Do not connect the fan to a
damaged or hazardous power source. Do not attempt to resolve electrical malfunctions or failures on
your own. Contact Big Ass Fans if you have any questions regarding the electrical installation of this fan.
Wiring Diagram
Controller Input Cable
White +0–10 VDC Speed Ref.
Brown Not Used
Orange Status LED (+)
Yellow
Run Enable
Closed: Enable; Open: Disable
Blue
Green Status LED (-)
Red +10 VDC Supply
Black DC Common